Troubleshooting 13
13-8
B30A
Loading/
parameter
consistency error
The station type is different between
the module and the parameter.
Set the parameter correctly.
B30B
Loading/
parameter
consistency error
The loading status is not consistent
with the network parameters.
Align the loading status with the
network parameters.
B30D
Temporary error
invalid station
specification error
Before link starts up, temporary error
invalid stations are specified.
Start up the data link first, then
specify temporary error invalid
stations.
B384
Station number
setting error
(parameter)
The station number in the station
information (addresses 20
H
to 2E
H
)
(parameter) is not set inside the
range from 1
H
to 40
H
.
Set a station number inside the
specification range (1
H
to 10
H
) of the
FX Series master station.
B385
Total number of
modules setting
error (parameter)
The total number of occupied stations
in the station information (addresses
20
H
to 2E
H
) (parameter) is beyond 64.
Set the parameter inside the
specification range (15 or less) of the
FX Series master station.
B386
Number of
occupied stations
setting error
(parameter)
The number of occupied stations in
the station information (addresses
20
H
to 2E
H
) (parameter) is set to 0 for
every station.
Set the number of occupied stations
inside the range from 1 to 4.
B387
Unusable area
write error
Data was written to the unusable area
(unused) in the buffer memory.
Do not write to the unusable area
(unused) in the buffer memory.
B388
Station type
setting error
The station type in the station
information (addresses 20
H
to 2E
H
)
(parameter) is not set inside the
range from 0 to 2.
Set 0 or 1.
B389
Unusable area
write error
Data was written to the unusable area
(unused) in the buffer memory.
Do not write to the unusable area
(unused) in the buffer memory.
B38D
Error invalid
station
specification error
(parameter)
In the invalid station specification
(address 14
H
) (parameter), a station
number other than a module head
station number or a station number
not set in the parameter is set.
Example of station number other than
head station number:
For a module occupying 4 stations
(station Nos. 5 to 8), a bit not
corresponding to the station No. 5 is
set to ON.
Set a module head station number
Do not set a station number which is
not set in the parameter.
Table 13.2:
Error
code
(hex.)
Description
Cause of error (details)
Corrective action
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......