Appendix 14
14-1
14.
Appendix
Parameter setting sheet
Table 14.1:
Item
Setting range
Buffer
memory
address
Remarks
Default
Preset
value
Number of
connected modules
1 to 15
1
H
⎯
8
Number of retries
1 to 7
2
H
⎯
3
Number of automatic
return modules
1 to 10
3
H
⎯
1
Operation
specification against
CPU down
0: Stop, 1: Continue
6
H
⎯
0 (stop)
Reserved station
specification
Set to 1 the bits
corresponding to
reserved stations.
10
H
Station Nos. 15 to 1
0000
H
Invalid station
specification
Set to 1 the bits
corresponding to invalid
stations.
14
H
Station Nos. 15 to 1
0000
H
Station information
b15 to b12 (station type)
0: Remote I/O station
1: Remote device station
b11 to b8 (number of
occupied stations)
1: Occupies 1 station.
2: Occupies 2 stations.
3: Occupies 3 stations.
4: Occupies 4 stations.
b7 to b0 (station number)
01
H
to 1F
H
(1 to 15)
20
H
1st module
0101
H
21
H
2nd module
0102
H
22
H
3rd module
0103
H
23
H
4th module
0104
H
24
H
5th module
0105
H
25
H
6th module
0106
H
26
H
7th module
0107
H
27
H
8th module
0108
H
28
H
9th module
0109
H
29
H
10th module
010A
H
2A
H
11th module
010B
H
2B
H
12th module
010C
H
2C
H
13th module
010D
H
2D
H
14th module
010E
H
2E
H
15th module
010F
H
FX2N-16CCL-M CC-Link System Master Block
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......