FDC-HKXR
938
(5)
Cooling opetation down to -5˚C outdoor temperature
(6)
Indoor units are available with 9 capacities, in 9 types and 54 models.
●
9 capacities…22(0.8 HP), 28(1 HP), 36(1.25 HP), 45(1.6 HP), 56(22 HP), 71(2.5 HP), 90(3.2 HP), 112(4 HP) and 140(5 HP).
●
9 types…Ceiling recessed type(FDT), 2-way outlet ceiling recessed type(FDTW), 1-way outlet ceiling recessed type(FDTS),
Cassetteria type(FDR), Satellite ducted type(FDUM), Ceiling suspension type(FDE), Wall mounted type(FDK), Floor standing
exposed type(FDFL) and Floor standing hidden type(FDFU).
(7)
Vertical blow or horizontal blow type can be selected for the outdoor unit.
(8)
Long piping design offeres One way piping length of 100 m
●
Indoor and outdoor units can have a level difference of up to 50 m, with a one way piping length of up to 100 m. This is the top-
class long piping design in the industry. A level difference of as much as 15 m between indoor units ensures that the system can
meet a wide variety of air conditioning requirements in any building.
(9)
Layout free refrigerant piping
The branch type piping makes the system flexible enough to satisfy any layout plan on the floor or in a room.
(10) Improvement of serviceability
(a) Failures of indoor unit and outdoor units are shown on the liquid crystal display on the remote controller.
●
Failures of indoor unit and outdoor units can be checked by remote controller.
(b) Easy checking of outdoor inspection LED.
●
The LED can be checked without removing the service panel, and faulty units can be easily indentified out of several units.
Standard
horizontal blow
Vertical blow
Using an adapter
(Optional)
(3)
Installation of automatic address setting function
•
The address setting method are divided into three types according to wiring method: “Automatic Address Setting,”
“Remote control Address Setting.” and “Manual Address Setting.” In case of the Automatic Address Setting, no
address needs be set as usual.
(4)
Connectable indoor capacity
Capacity from 50% to 130% is possible.
•
FDCP2001HKXRE2
Number of connectable units: 1 to 8 units
Connectable capacity: 11000 ~ 29200 W
•
FDCP2501HKXRE2
Number of connectable units : 1 to 8 units
Connectable capacity: 13200 ~ 37100 W
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...