638
FDU-C
16
Remote controller mounting dimensions
47
7
Standard Within 0.3 mm
2
×
Within 100 m
0.5 mm
2
×
Within 200 m
0.75 mm
2
×
Within 300 m
1.25 mm
2
×
Within 400 m
2 mm
2
×
Within 600 m
Allowable rang of wire thickness and length
♦
Usable JIS box, JIS C 8336
⋅
Switch box for 1 piece (without cover)
(use of the mark hole as illustrated on the left)
⋅
Switch box for 2 pieces
(use of the mark hole as illustrated on the left)
(without cover)
(use of the mark hole as illustrated on the left)
(when installing the cover)
Note (1) Allowable length of remote controller
cable: 600 m
0.3mm
2
, 3cores (O.D.
φ
5.6)
LCD display
120
Wall
Wire
(Recessed)
Junction box
(Locally Purchased)
89
83.5
17
120
Remote controller outline
For the passage
after wiring
120
60
46
(2)
Remote controller (Optional parts)
Unit: mm