532
FDR-H
Item
Model
FDR308-A
FDC308HEN3
Decorative panel
Panel model (Option)
Nominal cooling capacity
(1)
W
7100
Nominal heating capacity
(1)
W
8000
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
3.02/3.22
Running current (Cooling)
A
14.0/14.5
Power factor (Cooling)
%
98/93
Heating input
kW
2.88/3.04
Running current (Heating)
A
13.4/13.8
Power factor (Heating)
%
98/92
Inrush current
A
95
Noise level
dB(A)
52
Exterior dimensions
mm
845
×
880
×
340
Height
×
Width
×
Depth
Net weight
kg
74
Refrigerant equipment
—
GT-A5534EN41
×
1
Compressor type & Q’ty
Motor
kW
—
2.5
Starting method
—
Line starting
Heat exchanger
Louver fines & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.4 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
—
1.45 (BARREL FREEZE 32SAM)
Defrost control
MC controlled de-icer
High pressure control
High pressure switch
Air handling equipment
Multiblade centrifugal fan
×
2
Propeller fan
×
1
Fan type & Q’ty
Motor
W
100
×
1
55
×
1
Starting method
Line starting
Air flow (Standard)
CMM
Hi: 20 Lo: 15
58
Available static pressure
Standard: 45 (4.5) High: 80 (8.0)
—
Fresh air intake
Available
—
Air filter, Q’ty
Polypropylene net
×
2 (washable)
—
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
—
33 (Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional : RCD-H-E)
— (Indoor unit side)
Room temperature control
Thermostat by electronics
—
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fanmotor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
—
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit, Drain hose
Optional parts
Decorative Panel
Model FDR308HEN-SA
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Canvas panel is used in combination with following canvas duct. Canvas duct: HA01503
(5) Main unit height of canvas specification type is higher than the other type for canvas duct portion.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
—
7˚C
6˚C
ISO-T1, JIS B8616
Operation data
(3)
Silent panel
R-PNLS-36W-E
Canvas panel
R-PNLC-36W-E
_
_
Hi: 44 Lo: 38
Hi: 45 Lo: 39
Unit: 355
×
950
×
635
Panel: 10
×
1240
×
750
Unit: (299
+α
)
×
950
×
635
Panel: 10
×
1064
×
585
Unit: 35
Panel: 8
Unit: 35
Panel: 6
Pa
(mmAq)
FDR308HEN-SA
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...