1063
FDC-HKXR
(6) Setting of unit address
Addresses can be set either with the automatic address setting, remote control address setting or manual address setting depending
on the combinations of address switches (see table) of the indoor and outdoor units. Operate the address switches before turning
power on.
At the shipment from factory, outdoor Nos. of the outdoor unit are set at 49, both the output and indoor Nos. of the indoor units
are set at 49 and the setting method is set for the automatic addressing.
Address No. setting
Set the setting SW1 - 4 on the indoor PCB and the setting SW1 and 2 on the outdoor PCB as listed below.
Notes (1) Outdoor No. is provided on the outdoor and indoor PCB's and indicates which outdoor unit is connected with
which indoor unit via a refrigerant pipe. Indoor and outdoor units connected with a refrigerant pipe must have
the same No.
(2) Indoor No. is used to identify a particular indoor unit. The No. should never be duplicated.
(a) Auto address setting
This setting is used when wiring on the basis of outdoor unit.
Outdoor unit
Outdoor No.
49
00 ~ 47
00 ~ 47
Indoor unit
Indoor No.
49
49
00 ~ 47
Address setting method
Auto address
Remote control address
Manual address
Outdoor No.
49
49
00 ~ 47
On indoor PCB
SW1, 2 (blue)
SW3, 4 (green)
SW1, 2 (green)
On outdoor PCB
For setting of indoor No. (orders of 10 and 1)
For setting of outdoor No. (orders of 10 and 1)
For setting of outdoor No. (orders of 10 and 1)
0 1
2
3
4
SW1(SW3)
Use 48 and 49 for setting the auto or remote
control address.
SW2 (SW4) Order of 1
SW1
(SW3)
order of 10
Order of 10
0 1
2
3
4
5
6
7
8
9
SW2(SW4)
Order of 10
Order of 1
Insert the tip of flat head
(precision) screwdriver
here and point the arrow
at a desired No.
0
00
10
20
30
40
1
01
11
21
31
41
2
02
12
22
32
42
3
03
13
23
33
43
4
04
14
24
34
44
5
05
15
25
35
45
6
06
16
26
36
46
7
07
17
27
37
47
8
08
18
28
38
48
9
09
19
29
39
49
0
1
2
3
4
A
Outdoor unit
No. 49
Indoor unit
Indoor unit
Remote controller
Remote controller
Remote controller
Indoor unit
Wires cannot be connected across
different refrigerant lines.
Indoor unit
A
A
A
A
B
B
B
B
B
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...