FDT(N)-H
Notes (1)
Operation block A B : Normal cooling operation for 16 minutes after operation is started.
Operation stops by thermostat when the set temperature is reached.
After 16 minutes, normal thermal drying operation starts.
Operation block C D : Operation as above is performed for 8 minutes.
After 8 minutes, normal thermal drying operation starts.
(2)
In normal operation, the temperature is checked at 8 minute intervals
after normal thermal drying
operation is started,
to determine which operation block is to the selected.
Operation block A thermal drying is carried out if the thermostat set temperature is constant.
4)
Dehumidifying operation (“THERMAL DRY”)
The compressor, the indoor fan motor and the outdoor fan motor
are operated intermittently under thermistor (ThI-A) control ac-
cording to the appropriate operation block, to provide cooling op-
eration for the dehumidifying.
Operation block
D
C
B
A
Set temp. by thermostat
Pattern of operation
O p e r a t i o n
block
Thermal drying starting
(for 8 or 16 minutes after operation started)
A
(16 minutes)
• Cooling operation (Thermostat ON)
• Indoor fan operating with the setting air flow.
• When the thermostat is turned off, the indoor fan operates
for 30 seconds with the Lo operation in the wind blowing
mode and then stops.
(8 minutes)
Continuous cooling operation (FM
I
:Lo)
B
(8 minutes)
CM, FM
0
FM
I
C
(8 minutes)
CM, FM
0
FM
I
(8 minutes)
CM, FM
0
FM
I
D
(8 minutes) All stoppage
5)
Hot spurt (Only heat pump type)
In the hot spurt mode, the control is conducted at the level +2 higher than the setting temperature at the start of heating operation.
The hot spurt is canceled either after the initial thermostat OFF, when the indoor heat exchanger temperature reaches 61˚C or 60
minutes after the start of the mode.
Room temperature (deg)
CM, FM
O
: ON
FM
I
: ON
Normal thermal dry operation
(after completion of thermal drying)
Low
-2
+3
High
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...