632
FDU-C
Item
Model
FDU408-A
FDC406CES3
Nominal cooling capacity
(1)
ISO-T1
W
10200/11300
ISO-T3
8900/9900
Power source
3 Phase, 380-415V 50Hz, 380V 60Hz
Cooling input
kW
3.96/3.96/4.88
Running current (Cooling)
A
7.8/7.8/9.4
Power factor (Cooling)
%
77/71/79
Cooling input
kW
4.30/4.30/5.38
Running current (Cooling)
A
8.4/8.4/10.1
Power factor (Cooling)
%
78/71/81
Inrush current (L.R.A)
A
45
Noise level
dB(A)
44/46
57
Exterior dimensions
mm
360
×
820
×
830
1250
×
950
×
340
Height
×
Width
×
Depth
Net weight
kg
49
80
Refrigerant equipment
–
RC5547ESE1
×
1
Compressor type & Q’ty
Motor
kW
–
2.61
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
–
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.55 (Pre-charged up to the piping length of 0m)
Refrigerant oil
r
–
1.63 (SUNISO 3GS)
High pressure control
High pressure regulator valve
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
2
Motor
W
200
×
1
60
×
2
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
27/32
100/110
Available static pressure
Pa
Standard: 100 (10), Max 200 (20)
–
(mmAq)
Fresh air intake
Available
–
Air filter, Q’ty
Field purchased
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
–
Operation control
Remote control switch
Operation switch
(Optional: RCD-C-E)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
19.05 (3/4
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit.
Optional parts
–
Operation data
(3)
Model FDU408CES-A
ISO-T1
ISO-T3
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1, JIS B8616
Cooling
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
Notes (1) The data are measured at the following conditions.
FDU408CES-A
Internal protector for compressor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Internal thermostat for fan motor.
Frost protection thermostat.
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...