FDC-HKX
926
Current cut is indicated and the compressor cannot operate
Notes (1) when a short-circuit or ground-fault occurs in the
compressor motor, the current cut function is also
activated.
If the insulation resistance is 10M
Ω
or more, it is
normal.
The insulation resistance may considerably drop
depending on the refrigerant volume in the
compressor, but this is not faulty.
(2) 1-2 seconds after a start :
FDC140 type : Approx. 14A
FDC224 type : Approx. 32A
FDC280 type : Approx. 37A
Model
35Hz
160 ~ 180
40Hz
180 ~ 210
65Hz
290 ~ 320
75Hz
330 ~ 360
95Hz
380 ~ 410
Frequency
Unit : V (AC)
Inverter output voltage
All models
(outdoor unit)
Disconnect the compressor wiring
The compressor can operate
Is the current
cut function activated?
YES
YES
YES
YES
Defective inverter
Defective inverter
Is the insullation
resistance of the compressor
(1)
proper?
NO
NO
NO
NO
Is the output
voltage of the inverter
normal?
(Refer to 933 page)
(Refer to 933 page)
When the compressor wiring is
performed, the unit can operate.
Isn't the stating
current
(2)
excessive?
Defective compressor
Defective compressor
Defective inverter
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...