FDC-HKXR
Following precautions must be observed when the model is adapted to R407C.
(1) Tools and related components should be changed when handling a different kind of refrigerant in order to prevent mixing of different oils.
Gauge manifold and charge hose, particularly, should never be used after using them for R22.
(2) Charge cylinder should not be used. Otherwise, the refrigerant composition may change when charging R407C into the cylinder.
(3) Refrigerant should be charged in the liquid phase from the container. Charging the refrigerant in the gaseous phase could change the
refrigerant composition substantially.
(4) Volume of refrigerant to be taken out in the liquid phase from the container should be up to 90% of necessary quantity (in weight percent)
as a standard.
(5) Refrigerant should not be replenished even if a leakage is discovered because it could change the refrigerant composition substantially.
When a leakage is discovered, replace with new refrigerant in the specified volume. However, it could be replenished temporarily in case of
an emergency.
(7)
Refrigerant charge amount
(a)
Additional; charge amount
Notes (1) When the refrigerant piping length exceeds the length that additional refrigerant charge is not required, charge
additional refrigerant based on to calculated amount of refrigerant per unit piping length.
(2) The unit is holding charge type that all of the refrigerant is charged in the outdoor unit and in the indoor unit only
a small amount of refrigerant is filled for prevention of the air entry.
Calculation of amount of refrigerant to be charged in local piping
The amount refrigerant additionally charged in local piping depends on connection pipe size but not on indoor unit type.
[Amount of refrigerant to be charged in the local piping = Actual length of liquid pipe
×
Amount of
refrigerant additionally charged per meter of liquid pipe]
[Example] Amount of refrigerant additionally changed = (I
1
×
0.12) + (I
2
×
0.06) + (I
3
×
0.03)
I
1
: Overall length (m) of
φ
12.7 liquid pipe
I
2
: Overall length (m) of
φ
9.52 liquid pipe
I
3
: Overall length (m) of
φ
6.35 liquid pipe
20.5.5 Electrical wiring
(a)
Outdoor unit power supply (A separate power supply is used for the indoor unit)
FDCP2001HKXRE2
FDCP2501HKXRE2
5.5/5.5
8.0/8.0
Item
Model
3-phase
380/415V
50Hz
Power supply
wiring thickness
(mm
2
)
46/54
47/58
40A100mA 0.1sec or less
50A100mA 0.1sec or less
Rated current
40/40
60/60
Switch capacity
30/30
50/50
Wire
length
(m)
Power
supply
Wire circuit breaker (A)
Thickness
(mm)
Screw type
M6
5.5/5.5
Ground wire
Short-circuit breaker
(Use for both pround/
overload and short-
circuit production)
(b)
Indoor unit power supply
FDCP2001HKXRE2
FDCP2501HKXRE2
2.0/2.0
37/37 2.0/2.0
20/20
20A30mA 0.1sec or less
Item
1-phase
220/240V
50Hz
Power supply
wiring thickness
(mm
2
)
Wire
length
(m)
Power
supply
Between outdoor
and indoor units
Between
indoor units
2 core
×
0.75 ~ 2.0
Same as
at left
Signal wire thikness (mm
2
)
Short-circuit breaker
(Use for both pround/
overload and short-
circuit production)
Wire circuit
breaker
rated current
(A)
Thickness of
power supply
wire between
indoorunits
(mm
2
)
20/20
Circuit
Breaker
Switch
luse
capacity
(A)
Supported
outdoor model
(1)
Power supply wiring
Item
Model
FDCP2001HKXRE2
FDCP2501HKXRE2
Additional charge amount
per 1 m of liquid pipe
Factory charge amount at time of shipment
φ
12.7
φ
9.52
φ
6.35
Outdoor unit
Indoor unit
Remarks
0.12 kg/m 0.06 kg/m 0.03 kg/m
11.0 kg
Holding charged
Additional refrigerant
Charge is not required
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...