33
SRK-GZ
(i)
Open the suction grille, then remove the lid.
(ii)
Remove the wiring clamp.
(iii) Pass the connecting wire to terminal block from behind of indoor
unit.
(iv) Connect the connecting wire securely to the terminal block.
1
Connect the connection wire securely to the terminal block. If
the wire is not affixed completely, contact will be poor, and it
is dangerous as the terminal block may heat up and catch fire.
2
Take care not to confuse the terminal numbers for indoor and
outdoor connections.
3
Affix the connection wire using the wiring clamp.
(v)
Fix the connecting wire by wiring clamp.
(vi) Attach the lid.
(vii) Close the suction grille.
(3)
Preparation of indoor unit
(a)
Mounting of connecting wires
(i)
Remove lid
(ii)
Remove cover, terminal block cover
(iii) Insert connecting wire to terminal block securely.
1
Insert connecting wire up to the terminal block securely. If
poor insertion of conductor may result in imperfect contact
between the conductor and the terminal causing heat genera-
tion which may result in fire hazard.
2
Be careful not to confuse terminal numbers of connecting
wire between indoor and outdoor unit.
3
Use wiring clamp for connection wiring to avoid loosening
of the wire.
(iv) Install cover, terminal block cover.
(v)
Install lid.
(b)
Protective taping
(Protect the cable with tape at the section where the cable passes through the hole opened on the wall.)
(c)
Forming of pipe
(Holding down the pipe at the root, change the pipe direction, extend it and adjust according to the
circumstance.)
[When the pipe is extended to left and taken out from the rear center]
(Drain pipe relocation procedure)
1. Remove the drain pipe.
2. Remove the drain cap.
3. Insert the drain cap.
4. Connect the drain pipe.
¡
Loosen the spring clamp
and securely insert the
drain pipe.
Note:If it is inserted insuffi-
ciently, water leakage
could result.
¡
Loosen the spring clamp
to remove.
¡
Remove by hand or use
cutting pliers, etc.
¡
Securely insert the drain
cap removed in the step
2.
Note:If it is inserted insuffi-
ciently, water leakage
S
SRK502Z-L
S
SRK25, 35GZ-L1
Terminal Block Cover
Connecting Wiring
Earth
Wiring
Terminal
Terminal Block
Wiring Clamp
Lid
Cover
Pull the part marked
while pushing
its part in the direction of allow so as to
dismount it. (Dismount or detach it for
each side).
1
Brown
For power supply, indoor outdoor
2
Blue
Connecting wiring
3
Black
Indoor/outdoor signal wire (Low voltage)
Yellow/Green
Earth wiring terminal
Note (1) Connection wiring should not exceed 15 m. If this length is exceeded, communication
errors are likely to occur between the outdoor and indoor units, which could stop the air
conditioner.
Suction grille
Connection wire
Wiring clamp
Terminal
block
Screw
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...