499
FDKN-H
(3)
Carry-in and installation of unit
(a)
Carry-in
1)
When carrying in the unit, carry it in as packed to the installation site as near as possible.
2)
If you are compelled to carry in the unit unpacked, cover it with a nylon sling so that it is not
damaged.
Note) Do not carry the unit by holding it at the supply air louver.
3)
When laying the unit on the ground after unpacking. place it with its front side up without fail.
(b)
Attaching of mounting plate
1)
The indoor unit weighs approx, 11 kg. Therefore, check whether the portion to install the unit can bear the weight of
unit. If it seems to be danger, reinforce the portion by a plate or a beam before installing the unit. It is not allowed to
install the unit directly on the wall. Whenever you install the unit, use the attached mounting plate.
For left rear take-out piping
For right rear take-out piping
1. Remove the drain hose.
2. Remove the drain cap.
3. Insert the drain cap.
4. Connect the drain hose.
Reference hole
WARNING
The indoors
Wall
The outdoors
Sleeve
Sealing plate
Sleeve
Piping
Drain hose
Level matching mark
For left running horizontal piping
For right running horizontal piping
For left running horizontal piping
For right running horizontal piping
This air-conditioner is so constructed that dew generated on the
backside is gathered in the drain pan to drain, therefore, do not
store the power cable, etc. at the higher place than the trough.
Trough
Wall
Wiring storage portion
Right
Rear
Down
Left rear
Left
• Find structural members (Intermediate pillar, etc.) suitable for mounting the unit,
then install the unit firmly while checking levelness.
A
• Adjust the level of mounting plate under the condi-
tion that four screws are tightened temporarily.
• Turn the mounting plate around the reference hole
to adjust the levelness.
• Install the unit where it can bear the weight with sufficient strength margin. In the case of
insufficient strength or insufficient installation work, the unit may fall and cause injury.
After forming of
piping and be-
fore tape wind-
ing, confirm that
the connecting
wire is securely
fixed to the ter-
minal table.
The piping can be taken out from the
rear, left, left rear, right and down.
• Make a downgrade (5
°
) from the indoors toward the outdoors.
(c)
Procedure for making hole on the wall
(d)
Forming of piping and drain hose
1)
Rear take out case
•
Forming of piping
•
Tape winding
• Hold the root portion of pip-
ing, change the direction then
expand and make forming.
• Wind the tape on the portion which passes
through the hole on the wall.
• Always make taping on the wiring which
crosses with the piping, if any.
2)
Cautions for left take-out and rear take-out case
a) Looking down
b) Procedure for changing drain hose
• Loosen spring type clamp to
remove.
• Remove by hand or pliers.
• Insert the drain cap which was
removed in procedure 2 se-
curely using a hexagonal
wrench, etc.
Note: When it is not inserted se-
curely, water leakage may
occur.
• Loosen the spring type clamp
to insert the drain hose se-
curely.
Note: When it is not inserted se-
curely, water leakage may
occur.
Model
FDKN208 · 258 type
FDKN308 type
Dimension
A
450
690
Содержание SRRM40HENG-L
Страница 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Страница 52: ...50 SRK GZ MEMO ...
Страница 94: ...92 SRK H MEMO ...
Страница 104: ...102 102 SRK C MEMO ...
Страница 180: ...178 SCM HG 4room MEMO ...
Страница 222: ...220 SCM HG 2room MEMO ...
Страница 234: ...232 SCM CG 2room MEMO ...
Страница 266: ...SCM C 264 MEMO ...
Страница 406: ...404 FDT N C MEMO ...
Страница 442: ...440 FDEN H MEMO ...
Страница 470: ...468 FDEN C MEMO ...
Страница 504: ...502 FDKN H MEMO ...
Страница 580: ...578 FDR H MEMO ...
Страница 698: ...696 V MULTI Models FDR258 A 308 A ...
Страница 724: ...722 V MULTI MEMO ...
Страница 1094: ...1092 FDC HKXR MEMO ...