76
Pre-Programmed Modes
•
Hazard Release: Steady
12.4.4 How the Panel Works in Mode 4
•
Activation of either Z-1 or Z-2 changes Hazard Area1 state from Idle to Alarm. NAC-1
turns on at Temporal. Release Timer-1 is started.
•
Upon expiration of Release Timer-1. RAC-1 is activated. NAC-1 turns on Steady.
•
A current limit on Z-5 means Abort Switch active. Release Timer-1 is held. NAC-1 turns
on at Temporal. Removal of the current limit on Z-5 means that Abort Switch is released.
Release Timer -1 resumes. Release Timer value depends on Abort Delay Type.
•
Short on Z-5 indicates Manual Release active. Manual Release Delay Timer - 1 (MDT-1)
is started. NAC-1 turns on at Temporal. Upon the expiration of MDT-1, NAC-1 turns on
steady and RAC-1 is activated.
•
Activation of either Z-3 or Z-4 turns the Hazard Area 2 state from Idle into Alarm. NAC-2
turns on at Temporal. Release timer-2 is started.
•
Upon expiration of Release Timer-2, RAC-2 is activated. NAC-2 turns on steady.
•
A current limit on Z-6 means Abort Switch active. Release Timer -2 is held. Removal of
the current limit on Z-6, means releasing Abort Switch. Release Timer -2 resumes
running. Release Timer 2 value depends on Abort Delay Type.
•
Short on Z-6 indicates Manual Release active and Manual Release Delay Timer -
2(MDT-2) is started. NAC-2 turns on at Temporal. Upon the expiration of MDT-2, NAC-2
turns on steady and RAC-2 is activated.