65
Configuration
10.11 8. Test Dialer (Command-Menu)
10.11.1 Dialer Test Messages
The following messages will display during the test processes of Lines #1 and #2. The
messages that will appear depend on the status of the dialer and the test results that are
found.
Press Enter to test Line #1. Press Cancel to exit this menu. For
a description of test messages, see
below.
Press Enter to test Line #2. Press Cancel to exit this menu. For
a description of test messages, see
below.
This feature flushes all reportable events from the buffer. Press
Enter to reset the dialer. Press Cancel to exit this menu.
The dialer is checking the line for voltage. This message
automatically displays when Manual Test is selected.
No DC line voltage. The line is dead or no phone line is connected.
The dialer is waiting for a dial tone.
This message may indicate a noisy telephone line.
-Dialer Test-
1. L#1 Manual test
2. L#2 Manual test
3. Reset Dialer
L#1 Manual test
L#2 Manual test
3. Reset Dialer
Dialer idle now
No DC Volt
Waiting for Dialtone
Failed: No Dialtone