71
Pre-Programmed Modes
12.2
Mode 2: Agent Release, Single Hazard, Not Cross-zoned,
Combined Release
12.2.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -3: Alarm (Water-flow or pressure switch)
•
Detection Zone -4: Supervisory (default non-latching)
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release
•
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch
active.
•
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit
(optional).
•
RAC-1: Releasing Circuit (Hazard Area 1)
•
RAC-2: Releasing Circuit (Hazard Area 1)
12.2.2 Hazard Configuration
•
Default Release Timer Value: 60 seconds
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type: Standard UL.
•
Default Soak Timer Value: 0 seconds
12.2.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
Hazard Idle: Off
•
Hazard Alert: Temporal (see Table 7)
•
Hazard Alarm: Temporal
•
Hazard Release: Steady
•
Default NAC code of Supervisory Signal is 20 BPM.
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
WF
Sup
AB
MR
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
X
X
X
Out2
Signal
Escalating
X
(X)
X
Out3
Rel.
Releasing
X
X
Out4
Rel.
Releasing
X
X
RLS TMR 1 Started
X
X
RLS Tmr 1 Interrupted
X
RLS Tmr 1 Cancelled
X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled