81
Pre-Programmed Modes
12.7.4 How the Panel Works in Mode 7
•
Activation of either Z-1 or Z-2 changes Hazard Area 1 state into Alert. NAC-1 turns on at
Temporal.
•
Activations of both Z-1 and Z-2 change Hazard Area 1 state into Alarm. Release Timer-
1 is started. Upon the expiration of Release Timer-1, RAC-1 is active. NAC-1 turns on
steady.
•
Activation of either Z-3 or Z-4 changes Hazard Area 2 state into Alert. NAC-2 turns on at
Temporal.
•
Activations of both Z-3 and Z-4 changes Hazard Area 2 state into Alarm. Release Timer
2 is started. Upon the expiration of Release Timer 2, RAC-2 is active. NAC-2 turns on
steady.
•
Activation of Z-6 turns both NAC-1 and NAC-2 steady.
•
Activation of Z-5 can be indicated on NAC-2, if enabled.