16
4.0
System Components
4.1
Main Pre-Action/Deluge and Agent Release Control Panel
The following models are part of the FR-320 Series:
•
FR-320
•
FR-320-W
•
FR-320-R
•
FR-320-DW
•
FR-320-DR
Figure 1 FR-320 Panel
All FR-320 Panels have the following features:
•
Six Zone Pre-Action/Deluge and Agent Release Control Panel with LED display (red or
white door, black box.
•
six Class B (Style B) initiating circuits, and four Class B (Style Y) output circuits
•
Output circuits 1 & 2 are Class B (Style B) indicating circuits that can be converted to
Class A (Style Z) using an
OCAC-302 Output Class A Converter
adder module.
•
Output circuits 3 & 4 are Class B (Style B) only releasing circuits.
•
Each output circuit can draw 1.7A current, 5A total. A six zone
ICAC-306 Input
Class A
Converter
adder module may be used for Class A (Style D) wiring of Initiating circuits.
•
The FR-320 contains Common Alarm, Common Supervisory & Common Trouble
Relays, auxiliary alarm relay (disconnectable), an RS-485 Interface for Remote
Annunciators and a Resettable Four Wire Smoke Detector Power Supply.
•
Two batteries are required.
Additionally:
•
FR-320-DW/R panels contain a dialer.
•
FR-320 uses a BBX-1024DS or BBX-1024DSR enclosure.