82
Pre-Programmed Modes
12.8
Mode 8: Pre-action/Deluge, Dual Hazard, Not Cross-zoned,
Split Release
12.8.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -3: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -4: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -5: Supervisory
•
Detection Zone -6: Water-flow.
•
NAC -1: Escalating Signal, indicates Hazard Area 1 status
•
NAC -2: Escalating Signal, indicates Hazard Area 2 status
•
RAC 1: Releasing Circuit (Hazard Area 1)
•
RAC -2: Releasing Circuit (Hazard Area 2)
12.8.2 Hazard Configuration
•
Default Release Timer Value: 0 seconds
•
Default Manual Release Delay: 0 seconds (not used)
•
Default Abort Delay Type: Standard UL (not used)
•
Default Soak Timer Value: 0 seconds (continuous)
12.8.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
Hazard Idle: Off
•
Hazard Alert: Temporal (see Table 7)
•
Hazard Alarm: Temporal (see Table 7)
•
Hazard Release: Steady
•
Default NAC code of Supervisory is 20 BPM.
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
Alm
Alm
Supv
WF
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
X
X
Out2
Signal
Escalating
X
X
X
Out3
Rel.
Releasing
X
Out4
Rel.
Releasing
X
RLS TMR 1 Started
X
X
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
X
X
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled