32
Field Wiring
7.5
Four-Wire Smoke Detector Wiring
Figure 19 Four-wire smoke detector wiring
7.6
Relay Adder Module Wiring
Wire relays on the relay adder module RM-306 as shown in
Figure 20 Relay per zone (RM-306) Terminal connection
POWER
DETECTION
+
+
+
+
-
-
-
-
1
4
2
3
5
6
TO INITIATING
CIRCUIT
RESETTABLE 4-WIRE SMOKE
DETECTOR POWER SUPPLY
22VDC, 200mA
MAX. CURRENT - 300mA
MAX. RIPPLE VOL. 5mV
(POWER LIMITED)
4-WIRE DETECTION DEVICE
END OF LINE RELAY
LISTED S3403
MODEL A77-716B
MANUFACTURED BY
SYSTEM SENSOR
+
-
4-
W
IRE
SUPPL
Y
3.9K 1/2 WATT ELR
LEGEND
NOTES
ALL
POWER LIMITED
CIRCUITS
MUST USE TYPE FPL, FPLR,
OR FPLP POWER LIMITED
CABLE
FIRE ALARM MAIN BOARD
C
C
NO/NC
NO/NC
C
NO/NC
ALL RELAY CONTACTS
28V DC, 1 AMP
RESISTIVE LOAD
RM-306 6 RELAY ADDER MODULE
NORMALLY OPEN OR
NORMALLY CLOSED
CONNECTION IS
SELECTED BY JUMPER
ON RELAY BOARD.
NOTE: ALL RELAYS ARE POWER LIMITED
CIRCUITS AND MUST USE TYPE FPL, FPLR or
FPLP POWER LIMITED CABLE.
NORMALLY OPEN
CONNECTION
NORMALLY CLOSE
CONNECTION
RELAY
CIRCUIT #1
RELAY
CIRCUIT #2
RELAY
CIRCUIT #6