Pre-Programmed Modes
12.11.4 How the Panel Works in Mode 11
•
The activation of either Z-1 or Z-2 turns NAC-1 on steady.
•
The activations of both Z-1 and Z-2 turn NAC-1 off and turn NAC-2 on at 60BPM.
Release Timer-1 is started.
•
Expiration of Release Timer-1 results in the activation of RAC-1 and RAC-2. NAC-2
turns on steady.
•
If Z-5 is active, when the Release Timer-1 is running, NAC-2 turns off and NAC-1 turns
on Steady. The Release Timer is held.
•
If Z-5 is released, NAC-1 turns off and NAC-2 turns on 60BPM. Release Timer-1
resumes running. Release Timer value depends on Abort Delay Type.
•
Activation of Z-6 starts Manual Release Delay Timer-1(MDT-1). Upon the expiration of
MDT-1, RAC-1 and RAC-2 are active. NAC-2 turns on steady.
•
Activation of Z-3 turns NAC-2 on steady.
•
Activation of Z-4 can be indicated on NAC-2 at 20BPM, if configured.