102
Appendix E: Specifications
Unfiltered supply
(full wave rectified)
Power limited / Unregulated / Special Application
1.7A Max, 21.3 VDC to 42.00 VDC
Minimum Load 5mA
Battery
Type
24VDC Gel Cell/Sealed lead acid – 10AH to 26AH
Charging capability
10AH to 26AH
Protection
10A on board (F1) slow blow micro fuse
Compliance
System Model
FR-320 Series Control Unit - Fire Alarm, for
Releasing services
System Type
Local Auxiliary (using PR-300), Remote Protected
Premises Station (using PR-300 or FR-320-DR/DW).
Central Station Protected Premises (using FR-320-
DR/DW.) For ULC application also use PR-300 for
alternate communication path.
Type of Service
A, M, WF, SS
Type of Signalling
Non-Coded
Applicable Standards
NFPA 12, 12A, 12B, 12, 15, 16,70,72,2001, UL-864
Rev. 9, ULC S-524, ULC S-527-11
Table 11 FR-320 System Modules and Annunciators
FR-320
System Modules and Annunciators
RM-306
Relay Adder Module
Must be connected to a listed power-limited
source of supply.
Contact rating
FormC/ 28VDC per contact / 1A resistive load
max, zoned
Current consumption
standby 0mA, alarm 80mA
ICAC-306
Input Class A Converter module
standby: 0mA / alarm: 0mA
OCAC-304
Output Class A Converter Module
standby: 0mA / alarm: 0mA
SRM-312
Smart Relay Module
Must be connected to a listed power-limited
source of supply
Contact rating
FormC/ 28VDC per contact /
1A resistive load max, zoned
Current consumption
standby 30mA / alarm
140mA
Contact rating
FormC/ 28VDC per contact / 1A resistive load
max, zoned
Current consumption
standby 30mA, alarm 140mA
RAM-208
8 Zone Remote Annunciator
Standby 35mA / alarm 90mA
Table 10 FR-320 Series Specifications (Continued)