[Number of load cells]
Number of load cells connected in parallel
Input: 1, 2 <4> 9, 10
[Nominal load]
Maximum capacity E
max
of a load cell (not the total maximum capacity of the scale!)
Input: For the value refer to the technical data of the load cell.
[Gravity]
Gravity at place of installation
Default is the value for Hamburg, Germany: 9.81379 m/s
2
.
[Hysteresis error]
Hysteresis error
When switching from [not specified] to [specified] values for [Correction A/B] must
be entered. For this data refer to the load cell certificate.
[Certified data], [LC sensitivity], [LC resistance]
When [all LC same] is set, only one value for the characteristic value [LC sensitivity]
and the output resistance [LC resistance] are required.
For [each LC specific] press the [Enter] softkey to enter individual data for each load
cell.
7.12.10
Subsequent dead load correction
If the hopper/platform weight changes by an amount that is higher than the zero-setting
range; e.g. due to dead load reduction, dead load increase, or mechanical changes, the
functions for automatic zero tracking and manual zero setting no longer work.
2.
Press the [Calc] softkey to start the calculation.
3.
Confirm the calculation by pressing the [Ok] softkey to save the calculated mV/V
value to the calibration data.
7 Commissioning
Transmitter Series PR 5220
EN-85
Minebea Intec
Содержание PR 5220 Series
Страница 26: ...3 6 Overview of connections 3 Device description Transmitter Series PR 5220 EN 23 Minebea Intec ...
Страница 234: ......