Parameter table
Menu item
Selection
Description
[no output]
Analog output is unused.
[Gross D08]
Output of the gross weight.
[Net if tared D09]
Output of the net weight, if tared; otherwise gross
weight
[Selected D11]
Output of the gross/net value on the display, de-
pendent on SPM bit X72.
[Analog mode]
[Transparent D30]
Output of the value in D30
[0 20 mA]
Output of 0 20 mA.
[Analog range]
[4 20 mA]
Output of 4 20 mA.
[0 mA]
Set output to 0 mA.
[4 mA]
Set output to 4 mA.
[20 mA]
Set output to 20 mA.
[Output on error]
[hold]
The last output value is held.
[0 mA]
Set output to 0 mA.
[4 mA]
Set output to 4 mA.
[20 mA]
Set output to 20 mA.
[Output if < 0]
[linear]
The output drops below 4 mA down to the limit (at
4 20 mA).
[0 mA]
Set output to 0 mA.
[4 mA]
Set output to 4 mA.
[20 mA]
Set output to 20 mA.
[Output if > Max]
[linear]
Output increases above 20 mA until the limit is re-
ached.
[Weight at 0/4 mA]
Weight value for 0/4 mA output.
[Weight at 20 mA]
Weight value for 20 mA output.
Quit the menu and save parameters by pressing
.
Note:
Adapting the analog output, see Chapter
7.16 System information
This menu displays system information.
You can also check inputs and outputs, see Chapter
Press
to access the menu.
Transmitter Series PR 5220
7 Commissioning
Minebea Intec
EN-150