counting down. To troubleshoot most errors, suspend the formula in progress and turn power off.
Do not terminate the formula if it is to be resumed after the error is corrected. See
Shorten, Terminate, or Suspend a Running Formula
for more information.
Display or Action
Explanation
DOOR NOT CLOSED
This error message indicates that the door input is not made while
the machine is running. Verify that the door is closed, then check
the door switch and its connection to the microprocessor. Press
if necessary to resume operation after the error is corrected.
Never operate this machine while this message is present.
CHECK LEVEL SWITCH
The level switch may be faulty, perhaps reporting that level 2 was
achieved before level 1. Check the pressure transducer, or the lev-
el switch and its input connection to the microprocessor.
LEVELS STILL MADE
The microprocessor is still receiving information that a level is
made just before or during an extract step, or immediately before
the fill for a bath step. This error is self-clearing when level is
lost.
TOO LONG TO FILL
For software WUH7JA, this error indicates that the time to fill to
level exceeded 10 minutes. Check the water valves, strainers, sup-
ply lines, and water pressure. The machine will continue to fill un-
til level is reached, at which time the error will automatically clear
and normal operation will resume. This software is used on
30022X8J machine models.
For software WUV7J1B with version 2300K and later, you can
configure the time before this error appears. This software is used
on all machines with V_J in the model number, as well as
36026X8J and 420__X7J machine models.
•
If configure decision
Fill Error Time
is set to
00
, then the
machine will continue to fill until the programmed level is
reached.
•
If configure decision
Fill Error Time
is set to a value greater
than 00, the machine will signal the error and turn off the
water valves. The operator can choose to reset the error timer
and try to fill again or to cancel the formula.
Cancel the formula.
Reset the fill error timer and try to fill again
TOO LONG TO STEAM
The configured maximum time to steam up to the desired temper-
ature has been exceeded. Check the steam valve, strainer, main
steam header and pressure, etc. Steaming will continue until tem-
perature is achieved, when the error will automatically clear and
normal operation will resume.
TOO LONG TO COOL
The configured maximum time to cool down to the desired tem-
perature has been exceeded. Check the cooldown valve and
strainer if equipped, cold water pressure, and position of vernier