5-66
MICRONIX USA, LLC
www.micronixusa.com
Rev: 3.02
Set Feedback Constants
During Motion
Real-time
Program
Global
Set
Read
Set
Read
Set
Read
Set
Read
Command
Description:
This command is used to set the encoder feedback constants for
a specified controller.
Returns:
A read operation returns the encoder feedback constant values
for the specified axis.
Syntax:
nPIDx1,x2,x3
–
Standard syntax
nPID?
–
Read encoder feedback constant values
Error(s):
PIDx1,x2,x3
–
Missing axis number [30]
PID
?
–
Read operation with missing axis number [27]
nPID
–
Missing encoder feedback constant parameters
[28]
Parameter
Description:
n[int]
–
Axis number
x1[float]
–
K
p
(proportional term)
x2[float]
–
K
i
(integral term)
x3 [float]
–
K
d
(derivative term)
?
–
Read encoder feedback constants and values
Parameter
Range:
n
–
1 to 99
x1
–
0.000 to 1.000
x2
–
0.000 to 1.000
x3
–
0.000 to 1.000
Related Commands: FBK, ENC, POS
Example:
5PID.02,.04,.05
|
Axis 5, Set encoder feedback constants to 0.02,
0.04 and 0.05, respectively
-
2PID.03,,
|
Axis 2, Set encoder feedback constant K
p
to
0.03, other constants remain unchanged
-
4PID,,.07
|
Axis 4, Set encoder feedback constant K
d
to
0.07, other constants remain unchanged