14
Programming—IFC-1010/2020 Programming
Table 2: Partial System Programming Submenu
Partial System
Programming
Submenu
Description
1=INST
Installation
Installation or removal of the SLC loop interface boards from memory.
2=STY
Style
Changing (in memory) the National Fire Protection Association (NFPA) style of the SLC
loops.
3=TDLY
Time Delays
Setting the time delays for Alarm Verification, Signal-Silence Inhibit, and Signal Cut-Out.
4=AVPS
Audio/Visual Power Supplies
Telling the IFC-1010/2020 how many Audio/Visual Power Supplies are installed in the
system. The AVPS-24 and AVPS-24E have been replaced by the APS-6R.
5=ZBND
Zone Boundary
Setting the zone boundary for the software memory map.
6=EXTEQ
External Equipment
Changing the external equipment options, such as electrical supervision of the CRT monitor.
7=LOCP
Local Parameters
Setting local parameters, such as enabling or disabling the piezo sounder during point
programming of SLC loop devices, LIB Local mode, and NFPA programming.
8=ISIB
Intelligent Serial Interface Board
Installation or removal of the Intelligent Serial Interface Board (SIB-2048[A], SIB-N2, or
SIB-NET) or annunciator modules (for a description of annunciator modules, refer to the
Serial Communications
section of the
IFC-1010/2020 Installation
Technical Bulletin
[LIT-448155]
). Also used to enable the external interface for upload/download, and Universal
Digital Alarm Communicator Transmitter (
4=DACT
– UDACT Installation) selection.
9=PARM
Additional System Parameters
Selection of additional system parameters such as the detector day/night sensitivity settings
and rapid polling.
See Figure 8 for the Partial System Programming menu flowchart.
Detailed information on the Partial System Programming options follows.
Notes: When removing loop interface boards, all installed points on the
affected LIBs are automatically removed upon cycling power to the
system. Store programming information for installed points in a
FIRE PRO or VeriFire database prior to removal of the LIB. Using
the FIRE PRO or VeriFire application for the reprogramming of
previously removed points is highly recommended.
When removing annunciator modules, all installed points on the
affected annunciators must be removed first for proper system
operation.