Figure 80: CBE Equations
CCBE equations pertain to reverse activated software zones on the
IFC-1010/2020 the Metasys Fire Network system only.
CCBE, like CBE, is used to provide a variety of responses based on
various combinations of events (initiating conditions). Where CBE
programming controls the interaction between devices and software zones
within one IFC-1010/2020, CCBE programming controls events between
multiple panels on a Fire Network system. An example of this is an
initiating device in one panel turning on an output device of another panel
through a reverse activated software zone. The formats and uses for CBE
and CCBE are similar in many ways with the following exceptions:
•
Only reverse activating (RZON) software zones can be programmed
with a CCBE equation.
•
CCBE equations can be programmed only for software zones from the
IFC-1010/2020 node in which the zones reside. For instance, if a
CCBE equation is to be programmed for software Zone 23 of Node 10,
the user must program the equation on the IFC-1010/2020 that is
declared as Node 10.
•
CCBE can use only the
AND(
,
OR(
, and
NOT(
operands.
•
CCBE equations have a size limitation of 80 characters.
Note: Forward activating software zones (FZON)
cannot
have CCBE
equations but can be used as operands in other CCBE equations.
Cooperative
Control-By-
Event