10
Programming—IFC-1010/2020 Programming
!
1
&
7
Y
Y
Y
Backspace
Initpo2
Figure 4: Key Sequence to Avoid Piezo Sounding
When the first device has been programmed into the system, the
control panel reports a trouble condition and will exit Programming
mode.
IMPORTANT:
Do not acknowledge this trouble.
Reenter programming and the control panel will no longer exit
programming or sound the piezo for subsequent trouble conditions.
N1
Continue in the programming mode.
•
For initial system programming, read the
Full System Programming
section in this document and answer all the questions in that section
before entering programming mode. Then, enter Full System
Programming and load all the answers into the control panel.
•
Enter Full Point Programming. Use the worksheets developed in the
second step of this outline and enter information on all points in the
system. Program points in the following order:
1.
annunciator points
2.
zones
3.
detector points
4.
module points
•
When devising Control-By-Event (CBE) equations for a particular
device, remember that the label of the first software zone in the
equation of each addressable initiating device appears on the panel
display, along with the label of the device, when an alarm condition
occurs. For more information, see the Label (LBL) option in the
Label
section in this document.
•
Enter the System Message.
•
Install all devices and thoroughly test the entire system. Use the Walk
Test feature to test devices and their programming.
•
Make a hard copy record of the program on the printer.
If desired, upload the program to store on an external device (computer
hard drive or floppy) using the FIRE PRO or the VeriFire
programming
utility.