Programming—IFC-1010/2020 Programming
23
The following programming example illustrates the enabling of all
external equipment functions except the transmission of data during
printer error conditions, bidirectional copy, primary printer trouble error
reporting, and redirecting printer reports to the CRT.
PRESS 1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM : 6
DO YOU WANT TO CHANGE THE TERMINAL SUPERVISION? (Y=YES,N=NO) : Y
DO YOU WANT THE TERMINAL SUPERVISION ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE TERMINAL STATUS LINE? (Y=YES,N=NO) : Y
DO YOU WANT THE TERMINAL STATUS LINE ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE AUXILIARY PRINTER PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT THE AUXILIARY PRINTER ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE CONTROL MODULE STATE REPORTING? (Y=YES,N=NO) : Y
DO YOU WANT TO REPORT CONTROL MODULE STATE CHANGES? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE NONA/NOA MODULE STATE REPORTING? (Y=YES,N=NO) : Y
DO YOU WANT TO REPORT NONA/NOA MODULE STATE CHANGES? (Y=YES,N=NO) : Y
WERE ALL ADDRESSABLE DEVICES FACTORY-PURCHASED AFTER 4/1/91? (Y=YES,N=NO) : Y
DO YOU WANT TO ENABLE LED LATCHING FOR MORE DEVICES? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE PRINTER ERROR HANDLING? (Y=YES,N=NO) : Y
DO YOU WANT TO TRANSMIT DATA UNDER PRINTER ERROR CONDITIONS?
(Y=YES,N=NO) : N
DO YOU WANT TO CHANGE BIDIRECTIONAL COPY PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT BIDIRECTIONAL COPY ENABLED? (Y=YES,N=NO) : N
DO YOU WANT TO CHANGE THE PRIMARY PRINTER PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT THE PRIMARY PRINTER TROUBLE INHIBITED? (Y=YES,N=NO) : N
DO YOU WANT TO CHANGE THE PRINTER REPORT HANDLING? (Y=YES,N=NO) : Y
DO YOU WANT TO REDIRECT PRINTER REPORTS TO THE TERMINAL? (Y=YES,N=NO) : N
NEW ALM: 0000 TOT ALM:0000 NEW L:0000 TOT TBL:0000 –
Terminal Status Line
Figure 19: Programming to Enable External Equipment Functions
The terminal status line also displays signal silence information in the
same manner as the Signal Silence LED. The Signal Silence field displays
the messages
ALL SILENCED, PARTIAL SILENCE,
or is blank for
a non-silenceable system.
ALARM: SMOKE(PHOTO) COMPUTER ROOM 03:58P 03/01/97 101
SIGNAL SILENCE REQUESTED 03:58P 03/01/97 101
NEW ALM: 0001 TOT ALM: 0001 NEW TBL: 0000 TOT TBL: 0000 ALL SILENCED
The IFC-1010/2020 offers an LED-latching option:
DO YOU WANT TO ENABLE LED LATCHING FOR MORE DEVICES? (Y=YES,N=NO):
If you respond N, the control panel will employ a default latching
algorithm. If you respond Y, optional latching for more devices is
employed.
LED Latching