Programming—IFC-1010/2020 Programming
71
These options allow the programmer to generate the desired Walk Test
report. These reports are generated on a LIB basis. They use the same
display format as the Point Read option under Read Status except for the
status field, which is report-specific (no CBE or annunciator point
mapping is reported). The results of the report do not appear on the CRT
screen but are printed on the printer.
1=REQUEST Begins the selected report.
2=ABORT
Aborts the selected report in progress.
Note: Only one report can be conducted at any one time.
!
WARNING: Do not reset the Control Panel while in Walk Test
mode. Execution of a System Reset during a
Walk Test may cause unwanted activation of various
output modules (such as M5x0CJ, M300CJ, M300RJ,
XPC-8, XPR-8, and XP5-C). If a System Reset occurs
during a Walk Test, exit Walk Test mode and re-enter.
The following CRT screen illustrates conducting a Tested Device report.
PRESS 1=SEL,2=UNP,3=UNI,4=TEST,5=UNTST,6=EXIT : 4
ENTER LIB NUMBER FOR WALK TEST REPORT (1 - 10) : 1
PRESS 1=REQUEST,2=ABORT :
LIB 01 TESTED DEVICE REPORT BEGIN 04:32P 03/01/97
JOHNSON CONTROLS ALL SYSTEMS NORMAL 04:32P 03/01/97
LIB 01 TESTED DEVICE REPORT END 04:32P 03/01/97
JOHNSON CONTROLS ALL SYSTEMS NORMAL 04:32P 03/01/97
2=UNP –
Unprogrammed
Device Report
3=UNI –
Uninstalled
Device Report
4=TEST –
Tested Device
Report
5=UNTST –
Untested Device
Report