Figure 9: Key Sequence to Install an LIB
Select Option 1 from the Partial System Programming submenu to install
or remove LIB SLC loops from memory. The LIB boards still must be
physically installed or removed from the system to prevent a system
trouble condition. The Install Option flowchart is located in Figure 11. The
LIB capability is as follows:
•
The IFC-2020 is capable of a maximum of ten LIBs (1980 devices
total in the system).
•
The IFC-1010 is capable of a maximum of four LIBs (792
N18
SLC
devices total in the system).
The following programming example illustrates the installation of Loop
Interface Board (LIB) Number 3.
PRESS 1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM : 1
ENTER THE LIB BOARD NUMBER TO CHANGE (1 - 10)
: 3
IS LIB BOARD03 TO BE INSTALLED IN SYSTEM? (Y=YES,N=NO)
: Y
ENTER THE STYLE OF SLC LOOP 03 (6 OR 4)
: 6
DO YOU WANT TO CHANGE ANOTHER LIB BOARD? (Y=YES,N=NO)
: N
PROGRAMMING COMPLETE - POWER DOWN TO MAKE APPROPRIATE CHANGES
For information on LIB-400 and its correct slot address, refer to the
Installing the
IFC-1010/2020 Technical Bulletin (LIT-448155).