Programming—IFC-1010/2020 Programming
67
Note: Military time and conventional time are the same for the hours of
1:00 a.m. to noon. To convert conventional time to military time
for the hours of 1:00 p.m. to midnight remove the colon from the
conventional time and add the resulting number to 1200.
Example:
1:34 p.m. conventional time is 134 + 1200 = 1334 hours military
time (13 hours and 34 minutes).
On the Metasys Fire Network system, the time and date are
synchronized shortly after midnight by the lowest numbered
Metasys node. Every IFC-1010/2020 node, as well as the INA, will
be synchronized by the Metasys system.
????
Level 1 Password
alter5.cdr
%
5
Figure 60: Key Sequence to Access Option 5 (Diagnostics)
Option 5 from the Alter Status menu allows the programmer to perform
system diagnostics.
The Diagnostics Option submenu is shown below:
PRESS 1=RVER :
????
Level 1 Password
alter51.cdr
%
5
!
1
Figure 61: Key Sequence to Access Option 1 (Reset Counter)
This option allows the programmer to reset the detector verification
counters for all installed intelligent detectors. The detector verification
counter associated with each detector indicates how many times that
detector has entered the alarm verification routine without producing a
valid fire alarm.
The following example illustrates the execution of this option:
PRESS 1=RVER : 1
DO YOU WANT TO RESET THE DETECTOR VERIFICATION COUNTERS? (Y=YES,N=NO) : Y
Diagnostics
5=DIAG
1=RVER - Reset
Detector
Verification
Counters