Programming—IFC-1010/2020 Programming
57
Prog
%
5
????
Level 2 Password
sec15a.cdr
Figure 46: Key Sequence to Access Option 5
(Remove Devices)
Option 5 from the Programming menu allows the programmer to remove
(from control panel memory) SLC addressable devices, software-defined
zones, or annunciator points. The devices still can be installed in the
system, but the IFC-1010/2020 stops looking for these devices by not
polling them.
Notes: Devices that are removed will not function in any capacity until
they are reinstalled under Full Point Programming.
!
CAUTION: Devices that have had their LEDs latched on must be
returned to their normal state before removal (execute
System Reset for detectors or control Off for
modules). Unacknowledged points must be
acknowledged before removal.
The programming example below illustrates the CRT screen prompts
during removal of an SLC addressable device (Smoke Detector 34 on
SLC 10).
PRESS 1=PSYS,2=FSYS,3=PPRG,4=FPRG,5=REMV,6=PSWD,7=MSG,8=HIS : 5
ENTER LXX(D/M)YY, ZXXX OR AXXPYY FOR PT. REMOVAL (BCKSPC TO ABORT) : L10D34
Remove
5=REMV