Programming—IFC-1010/2020 Programming
39
If set, the control panel generates a trouble for each intelligent detector that
exceeds the verification counter trouble limit. This feature can be used to
isolate those devices, which excessively go into detector verification
before causing false alarm conditions in the panel. To clear this condition,
reset the detector verification counters by entering
Alter Status
,
selecting
5=DIAG
, then selecting
1=RVER
, and answering
Y
(Yes) to the
prompt.
If selected for reporting, module state changes for modules with the
Software Type ID SACM or SEQM are printed. For further information on
all Software Type IDs, refer to the
Software Type IDs
section in this
document.
If set, the addressable detectors automatically compensate for
environmental contaminants and other factors over time, until the drift
tolerance value has been exceeded. When the drift tolerance value has
been exceeded, the control panel signals a maintenance alert for the
appropriate detector.
The Pager mode must be enabled when a compatible pager is connected to
the auxiliary printer port.
If enabled, the following remote device (CRT) functions are inhibited:
Ack Step, Signal Silence, System Reset, Programming, and Alter Status.
This option must be employed when a modem is used to receive signals
from an off premise device.
N22
The NAM-232 is used to tie a remote FACP to the Fire Network via
telephone lines. If the NAM is enabled, the following options are
automatically programmed as indicated:
•
Terminal Supervision = Enabled
•
Terminal Status Line = Enabled
•
Receiving Unit Mode = Enabled
•
Event Reminder = Disabled
•
Reports Redirected to Terminal = Enabled
•
Modem = Disabled
This special application only supports the Acknowledge, Signal Silence,
and System Reset network functions and is intended for Protected
Premises Fire Alarm System (Local) use only. Local use of a CRT, printer,
or other 232 device from the remote FACP is prohibited. No other system
network functions can be implemented due to system constraints.
Detector
Verification
Trouble
SACM/SEQM
Module
Reporting
Drift
Compensation
Pager
Modem
NAM
N30