Programming—IFC-1010/2020 Programming
27
The following programming example illustrates the disabling of the
panel’s piezo sounder, programming LIB Local mode, modifying NFPA
listings, programming the battery parameters, and changing the event
reminder, device blink, and pre-alarm programming.
Note: The sounder must be enabled upon completion of programming.
PRESS 1=INST,2=STY,3=TDLY,4=AVPS,5=ZBND,6=EXTEQ,7=LOCP,8=ISIB,9=PARM : 7
DO YOU WANT TO CHANGE THE PIEZO TROUBLE CONDITION? (Y=YES,N=NO) : Y
DO YOU WANT THE PIEZO SOUNDER SILENCED WHILE PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE LIB LOCAL MODE PARAMETERS? (Y=YES,N=NO) : Y
DO YOU WANT TO PROGRAM LOCAL MODE? (Y=YES,N=NO) : Y
ENTER MAXIMUM ADDRESS FOR DETECTOR LOCAL MODE (1 - 99) : 99
ENTER MAXIMUM ADDRESS FOR MONITOR MODULE LOCAL MODE (1 - 99) : 99
ENTER MAXIMUM ADDRESS FOR CONTROL MODULE LOCAL MODE (1 - 99) : 99
DO YOU WANT TO MODIFY NFPA LISTINGS? (Y=YES,N=NO) : Y
SELECT NFPA LISTING - 1=72A,2=72B,3=72C,4=72D,5=71,6=RCV : 1
DO YOU WANT TO PROGRAM OR REMOVE THIS LISTING? (Y=PRG,N=RMV) : Y
DO YOU WANT TO MODIFY NFPA LISTINGS? (Y=YES,N=NO) : Y
SELECT NFPA LISTING - 1=72A,2=72B,3=72C,4=72D,5=71,6=RCV : 2
DO YOU WANT TO PROGRAM OR REMOVE THIS LISTING? (Y=PRG,N=RMV) : Y
DO YOU WANT TO MODIFY NFPA LISTINGS? (Y=YES,N=NO) : N
DO YOU WANT TO CHANGE THE BATTERY PROGRAMMING? (Y=YES,N=NO) : Y
ENTER THE TYPE OF BATTERY INSTALLED (L=LEAD-ACID,N=NICAD) : N
DO YOU WANT TO CHANGE THE BATTERY CAPACITY? (Y=YES,N=NO) : Y
ENTER THE BATTERY CAPACITY (9 - 32 IN 1 AHR INCREMENTS) : 12
DO YOU WANT TO CHANGE THE BATTERY STANDBY TIME? (Y=YES,N=NO) : Y
ENTER THE BATTERY STANDBY TIME (4, 24, 48 OR 60 HR) : 48
DO YOU WANT 24 HOUR HIGH RATE CHARGE FOR BATTERY? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE EVENT REMINDER PROGRAMMING? (Y=YES,N=NO) : Y
DO YOU WANT THE EVENT REMINDER ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE DEVICE BLINK? (Y=YES,N=NO) : Y
DO YOU WANT THE DEVICE BLINK ENABLED? (Y=YES,N=NO) : Y
DO YOU WANT TO CHANGE THE PRE-ALARM FUNCTION? (Y=YES,N=NO) : Y
DO YOU WANT THE PRE-ALARM FUNCTION ENABLED? (Y=YES,N=NO) : Y
The general operation of the piezo sounder includes:
•
The piezo sounder provides feedback each time a key is pressed on the
Display Interface Assembly (DIA).
•
The piezo sounder sounds a rapid pulsing for unacknowledged alarm
conditions.
•
The piezo sounder sounds steadily for unacknowledged trouble or
supervisory conditions.
•
The piezo sounder chirps periodically (approximately every
12 seconds) for acknowledged conditions remaining in the system
upon selection of the Event Reminder option.
General
Operation of
the Piezo
Sounder