Programming—IFC-1010/2020 Programming
21
Prog
!
1
^
6
????
Level 2 Password
Sec116a
Figure 17: Key Sequence to Change External Equipment
Option 6 from the Partial System Programming menu allows the changing
of any optional features associated with the CRT monitor or printers. See
Figure 18 for a flowchart diagram of the options available.
Table 3: Partial System Programming Menu
Partial System
Programming Menu
Description
Terminal Supervision
Electrical supervision of the CRT monitor. Unless terminal supervision is selected,
the CRT will not beep (for example, no bell characters will be sent) when
unacknowledged troubles or unacknowledged alarms are present.
Terminal Status Line
The bottom line of the CRT displays the number of unacknowledged alarms and
troubles and the total number of alarms and troubles in the system. The Terminal
Status Line appears on the CRT display only.
Auxiliary Printer
Monitoring
The IFC-1010/2020 will monitor the auxiliary printers Ready/Busy line for error
conditions.
Note:
The P40 is a special internal 40-column printer manufactured by Keltron,
as shown in the
Installing the
IFC-1010/2020 Technical Bulletin
(LIT-448155).
This option should not be enabled for external 80-column
printers (PRN-3 or PRN4).
Control Module Reporting
Control module state changes are printed out.
NONA/NOA Module
Reporting
Module state changes for modules with the Software Type ID NONA or NOA are
printed out. Refer to the
Software Type IDs
section of this document for further
information on all Software Type IDs.
LED Latch
Enables 99-device Light-Emitting Diode (LED) latching. Refer to restrictions in
LED Latching
of the
External Equipment
section of this document.
Printer Error Continue
Data will be transmitted to the printer under Printer Error conditions (Paper Out or
Printer Off Line generates an error condition under which data may be lost).
Bidirectional Copy
The CRT processes data received through its AUX port. Enable for special
applications only.
N28
Printer Trouble Inhibit
The IFC-1010/2020 monitors the primary printer's Rx line for error conditions. This
option inhibits the generation of a trouble message for Paper Out or Printer
Off Line. Enable for special applications only.
Printer Reports Redirected
to CRT
System reports will be echoed to the CRT interface. Enable for special
applications only.