98
Programming—IFC-1010/2020 Programming
L1D1 activates Z1 and Z2. L1D2 activates Z1, Z2, and Z3. L1D3 activates
Z2, Z3, and Z4. L1M1 activates when Z1 is active. L1M2 activates when
Z2 is active. L1M3 activates when Z3 is active. L1M4 activates when Z4
is active.
Z4
L1D1
Z2
L1D3
Z3
Z1
L1M2
M5x0CJ
L1M1
M5x0CJ
L1M4
M5x0CJ
L1M3
M5x0CJ
(Z1 Z2 Z3)
OR(Z1)
OR(Z2)
OR(Z3)
OR(Z4)
fffafb.cdr
Figure 85: Fire Floor Above, Floor Below
Node 1 activates L1M1 if Z1 is active locally. Node 1 activates L1M2 if
Z200 is active locally or in both Nodes 7 and 43 simultaneously. Node 43
activates L1M2 if Z200 is not active locally and if Z200 is not activated in
Node 7.
L1D2
RZON
Z200
RZON
Z200
(Z200)
OR()
OR()
L1D1
L1D2
RZON
Z200
L1M2
M5x0CJ
L1M2
M5x0CJ
L1M2
M5x0CJ
L1D1
L1D1
Z1
Z1
(Z1)
(Z200)
OR()
AND(N7200
N43Z200)
NOT(Z200)
(Z1)
(Z1)
OR()
OR(N7Z200)
OR(Z1)
OR(Z1)
OR(Z1)
L1M1
M5x0CJ
L1M1
M5x0CJ
L1M1
M5x0CJ
firenet
Node 1
Node 7
Node 43
Figure 86: CCBE for the Fire Network
Example 4:
Fire Floor,
Floor Above,
Floor Below
Example 5:
CCBE for the
Fire Network