76
Programming—IFC-1010/2020 Programming
Table 9: Addressable Detectors
Type ID
Display Label
Type of Device
ION
SMOKE (ION)
1x51J Intelligent Ionization Smoke Detector
IOND
ION DUCT DET
1x51J Intelligent Ionization Smoke Detector
with a
fixed sensitivity level. (The sensitivity of this
detector cannot be adjusted. All other detector
functions are equivalent to type ION). This detector
is used in conjunction with the DH500J duct
detector housing.
IONH
SMOKE ION HP
1251J Intelligent Ionization Smoke Detector.
(This software type can be used only in Canadian
applications and has the same programming
options as type ION.)
IONL
SMOKE ION LP
1551J Intelligent Ionization Smoke Detector.
(This software type can be used only in Canadian
applications and has the same programming
options as type ION.)
FPHT
FIXED PHOT D
2x51J Intelligent Photoelectric Smoke Detector
with a fixed sensitivity level. (This software type is
obsolete and should not be used.)
FTHR
FIXED THER D
5551J Intelligent Thermal Sensor
with a fixed
sensitivity level. (This software type can be used
only in Canadian applications and does not meet
UL sensitivity requirements for use in the U.S.)
PHOT
SMOKE (PHOTO)
2x51J Intelligent Photoelectric Smoke Detector.
The 2551J/751 photo detector does not require a
different software type when used with the DH500J
duct detector housing.
THER
HEAT (ANALOG)
5551J or 5551JR Intelligent Thermal Sensor
CMBO
SMOKE (COMBO)
3251J Intelligent Combination
Ionization/Photoelectric/Thermal Detector
Group 1