4.2 Position control mode
55
6. Smooth filter
The parameter P040 carries on the smooth filter to the command frequency. It has the
exponential form for acceleration and deceleration as showing in the following chart. The filter
cannot lose any input pulse, but can delay its action time. When P040 is zero, the filter does not
have any effect. The parameter value indicates the time in which the repeated frequency
increases from 0 to 63.2% command frequency.
The filter makes the input repeated frequency smooth. This filter is used in the following
situations: the host controller is without acceleration and deceleration function; the electronic
gear ratio is quite big; the command frequency is lower.