234
47DAC OPERATING MANUAL EM-9518-B Rev.4
■
INSTALLATION
Power consumption
AC power
100 – 240 V AC
Operational voltage range 85 – 264 V AC, 50/60 Hz
Approx. 8 VA at 100 V
Approx. 10 VA at 200 V
Approx. 12 VA at 264 V
DC power
24 V DC
Operational voltage range 24 V DC ±10%
Ripple 10% p-p max.
3.5 W max.
110 V DC
Operational voltage range 85 – 150 V DC
Ripple 10% p-p max.
3.5 W max.
Operating temperature
-10 to +55°C (14 to 131°F)
Operating humidity
30 to 90% RH (non-condensing)
Mounting
Panel flush mounting
Weight
300 g (0.66 lb)
■
PERFORMANCE
Accuracy
Display
±0.5% ±10 digits with input 5 – 100%
Output
±0.1% (DC output = d output)
Temp. coefficient
±0.05%/°C (±0.03%/°F)
Input resolution
Max. 19 bits
Output resolution
Max. 14 bits
Response time
≤ 0.5 sec. (alarm output: 0 – 100% at 90% setpoint)
≤ 0.5 sec. (DC output: 0 – 90%)
Line voltage effect
±0.1% over voltage range
Insulation resistance
≥ 100 MΩ with 500 V DC
Dielectric strength
2000 V AC @ 1 minute (input to DC output to HH output or H output to L output or
LL output to network or BCD output or event trigger input to power to ground)