47DAC OPERATING MANUAL EM-9518-B Rev.4
11.3 ALARM POWER ON DELAY
The measuring can begin after waiting for the delay time from power on. This time duration is called alarm power ON delay
and can be set within the range of 0.0 to 999.9 seconds. The default value is 0.0 second.
IMPORTANT
The changes on this setting are effective after power off and restart.
11.3.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Alarm/
↓
and Scale/
↑
buttons at once for 3 seconds
or more to move on to Advanced Setting Mode.
• The averaging type is indicated.
• The SD indicates ‘AVE-TP’.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).
2
Press Alarm/
↓
or Scale/
↑
button to go to the alarm power ON
delay setting.
• The alarm power ON delay is indicated.
• The SD indicates ‘PWR-DLY’.
3
Press Shift button to shift the display into the setting standby
mode. Then press Shift and Up buttons to set the alarm power
ON delay.
• The forth digit starts blinking, to which you can apply changes.
• Set within the range of 000.0 to 999.9.
1,2,
4,5
1,2,
4,5
3
3
Blinking