background image

156

47DAC OPERATING MANUAL EM-9518-B Rev.4

18.  DETECTING STEEP INPUT CHANGES

Only steep changes in the input signals can be detected with mild changes disregarded, which is called high-pass filter.  
Deviation between the currently measured input value and the average of the past values is calculated.
Table 2 shows the relationship between the sampling time and the reading.

 TABLE 1:  HIGH-PASS FILTER

MAIN DISPLAY

FUNCTION

DEFAULT VALUE

High-pass filter OFF

High-pass filter ON

 TABLE 2:  SAMPLING TIME V.S. READING

SAMPLING TIME

INPUT

READING

REFERENCE USED IN NEXT CALCULATION

1

I

1

I

1

 – I

1

 = 0

C

1

 = I

1

2

I

2

I

2

 – C

1

C

2

 = 

1

(C

1

 + I

2

) = 

1

(I

1

 + I

2

)

2

2

3

I

3

I

3

 – C

2

C

3

 = 

1

(C

2

 + I

3

) = 

1

(I

1

 + I

2

) + 

1

I

3

2

4

2

4

I

4

I

4

 – C

3

C

4

 = 

1

(C

3

 + I

4

) = 

1

(I

1

 + I

2

) + 

1

I

3

 + 

1

I

4

2

8

4

2

:

:

:

:

n

I

n

I

n

 – C

n-1

C

n

 = 

1

(I

1

 + I

2

) = 

1

I

3

 + …… + 

1

I

n

2

n-1

2

n-2

2

I

n

 :  Input

C

n

 :  Reference value used in the next round of calculation

*

1  Comparison is made against the result of last display (calculated) value.

• EXAMPLE (TABLE 3)

SAMPLING TIME

INPUT

READING

REFERENCE USED IN NEXT CALCULATION

1

5.0

5.0 – 5.0 = 0

5.0

2

4.0

4.0 – 5.0 = -1.0

1

(5.0 + 4.0) = 4.5

2

3

5.5

5.5 – 4.5 = 1.0

1

(4.5 + 5.5) = 5.0

2

4

4.0

4.0 – 5.0 = -1.0

1

(5.0 + 4.0) = 4.5

2

5

9.5

9.5 – 4.5 = 5.0

1

(4.5 + 9.5) = 7.0

2

*

2  Analog output may not simply increase/decrease depending upon timing of the input supplied in relation to the sampling rate.

Содержание 47DAC

Страница 1: ...s 47 Series AC INPUT DIGITAL PANEL METER 5 1 2 digit LCD display type true RMS sensing Model 47DAC OPERATING MANUAL http www m system co jp 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Tel 8...

Страница 2: ...4 WIRING INPUT SIGNAL 25 1 7 5 WIRING DC OUTPUT 26 1 7 6 WIRING ALARM OUTPUT RELAY 27 1 7 7 WIRING ALARM OUTPUT PHOTO MOSFET RELAY 28 1 7 8 WIRING NETWORK INTERFACE 29 1 7 9 WIRING BCD OUTPUT 31 1 7...

Страница 3: ...RATING PROCEDURE 66 5 OPERATION 69 6 PARAMETER CONFIGURATION 70 7 SETTING BARGRAPH 78 7 1 BARGRAPH TYPE 80 7 1 1 OPERATING PROCEDURE 80 7 2 BARGRAPH LOWER LIMIT UPPER LIMIT 82 7 2 1 OPERATING PROCEDUR...

Страница 4: ...PROCEDURE 118 10 3 BANK NO 120 10 3 1 OPERATING PROCEDURE 120 11 ADVANCED ALARM SETTING 121 11 1 P OUTPUT 124 11 1 1 OPERATING PROCEDURE 124 11 2 LATCHING ALARM 126 11 2 1 OPERATING PROCEDURE 126 11...

Страница 5: ...60 19 1 OPERATING PROCEDURE 161 20 ADJUSTING LCD CONTRAST 163 20 1 OPERATING PROCEDURE 164 21 SETTING EVENT TRIGGER INPUT 166 21 1 EVENT TRIGGER MODE 171 21 1 1 OPERATING PROCEDURE 171 21 2 ON TIMING...

Страница 6: ...DISPLAY VALUE TO ZERO 204 27 RETAINING MAX AND MIN VALUES 207 28 SETTING DISPLAY READING TYPE TO MAX OR MIN VALUE 209 28 1 OPERATING PROCEDURE 209 29 RETAINING MEASUREMENT STATUS 211 30 RESETTING MAX...

Страница 7: ...PERATING PROCEDURE 229 36 APPENDICES 230 36 1 SPECIFICATIONS 230 36 2 MODEL NUMBERING 235 36 3 PARAMETER LIST 236 36 4 PARAMETER MAP 242 36 4 1 OPERATION IN MEASURING MODE 242 36 4 2 SCALING SETTING M...

Страница 8: ...outlined below PACKAGE INCLUDES Digital panel meter Accessories Mounting bracket 2 Terminal cover 1 Watertight packing 1 tethered to the meter with a strap Engineering unit sticker label sheet 1 Instr...

Страница 9: ...ng is performed by qualified personnel only Failure to do so may result in a fire electric shock or injury Do not touch the terminals while the power is on Doing so may result in electric shock Check...

Страница 10: ...the unit while its power is on Doing so may result in electric shock malfunction or injury Do not allow fine shavings or wire scraps to enter the unit in machining screws or wiring Doing so may result...

Страница 11: ...name and polarity of each terminal before wiring to the terminal block Do not connect anything to unused terminals Be sure to attach the terminal cover to prevent electric shock HANDLING CAUTIONS The...

Страница 12: ...ertight packing included in the product package must be placed between the body and panel when installing on the panel Insert the unit into the panel cutout and fasten both mounting brackets tightly u...

Страница 13: ...M System s web site http www m system co jp TO READ WRITE 47DCFG CONFIGURATIONS VIA INFRARED COMMUNICATION Infrared Communication Adaptor model COP IRU optional It may take time to read write configu...

Страница 14: ...setpoints to move on to Alarm and other Setting Modes or to shift through setting items in each setting mode Scale Used to move on to the scaling and other setting modes or to shift through setting i...

Страница 15: ...depending on the parameters HH H L or LL indicator blinks corresponding to the P output setting Refer to 11 1 P OUTPUT Teach Calibration Zro or Spn indicator turns on and Tch indicator blinks in red R...

Страница 16: ...ifications The tag No label sticker position is our recommended position When a tag No is specified the unit s will be shipped with the tag No sticker label put on the above position Max 17 alphanumer...

Страница 17: ...fication label on the top of the unit Without Terminal Cover No Options Alarm Output RS 485 Modbus Strap Terminal block separable Terminal block separable Strap Terminal block separable BCD Output Eve...

Страница 18: ...AR VIEW No Options BCD Output Event Trigger Input Alarm Output Photo MOSFET Relay Alarm Output RS 485 Modbus FRONT VIEW SIDE VIEW TOP VIEW 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1...

Страница 19: ...Rev 4 1 6 2 PANEL CUTOUT DIMENSIONS 1 6 3 VIEWING ANGLE The display is designed to provide the optimal legibility when viewed from the angles as shown below unit mm 92 0 8 0 45 0 6 0 min 120 min 75 Pa...

Страница 20: ...b Pull the handle upward c Then insert the screwdriver into a hole at the lower right corner d Pull the handle upward to separate the terminal cover 2 Remove the mounting brackets a Flip a tab of a br...

Страница 21: ...it into the panel cutout 6 Push the mounting brackets into the grooves on both sides of the rear module until they hit the panel s rear side IMPORTANT To conform to degree of protection IP66 confirm v...

Страница 22: ...against induced lightning surges Please contact M System to choose appropriate models 1 7 2 SOLDERLESS TERMINAL AND WIRE INPUT DC OUTPUT ALARM OUTPUT RELAY NETWORK INTERFACE AND POWER INPUT RECOMMEND...

Страница 23: ...ose wire conductors by 7 to 8 mm 0 28 to 0 31 RECOMMENDED FERRULE The following Phoenix Contact terminals are recommended For single wire For twin wire CROSS SECTION AREA MODEL CROSS SECTION AREA MODE...

Страница 24: ...TIONS ALARM OUTPUT RS 485 MODBUS Input signal Power DC output Input signal Power DC output RS 485 Modbus Alarm output BCD OUTPUT EVENT TRIGGER INPUT ALARM OUTPUT PHOTO MOSFET RELAY Power DC output Inp...

Страница 25: ...nly In order to prevent potential electric shock wire the unit after cutting the input signal and making sure that the power is not supplied to the cable Do not connect anything to unused terminals IN...

Страница 26: ...stance within the specifications Do not connect anything with no DC output type Take measures to reduce noise as much as possible e g by using shielded twisted pair wires for the output signal Ground...

Страница 27: ...for AC or DC power in parallel to protect the contacts and eliminate noise I O options code 1 7 I O options code 2 8 15 16 17 18 19 20 HHa Ha Hc HHc La LLa Lc LLc H output LL output L output HH outpu...

Страница 28: ...or AC or DC power in parallel to protect the contacts and eliminate noise I O options code 3 9 11 12 13 14 15 16 HHa Ha Hc HHc La LLa Lc LLc H output LL output L output HH output NOTE Example of conta...

Страница 29: ...Internal terminating resistor is used when the device is at the end of a transmission line Install shield cables to all sections and ground them at single point for noise protection Connect in a dais...

Страница 30: ...232 C RS 232 C RS 485 Converter model R2K 1 or LK1 Lightning Surge Protector for RS 485 422 model MD74R or MDP 4R 1 Digital Panel Meter model 47Dx Max Min FZ TZ NG Zro Spn TG Hld Tch HH H P L LL Max...

Страница 31: ...mA Saturation voltage 0 3 V Leakage current 500 A HH H P L LL Alarm output signals NPN open collector Max load voltage 24 V DC Max load current 50 mA Saturation voltage 1 1 V Leakage current 500 A IMP...

Страница 32: ...V 9A RESET Reset data 9B Do28 BCD output data 8 101 10A HOLD Hold data 10B COM GND 0 V 11A MIN_REQ Request minimum reading data 11B Do24 BCD output data 4 101 12A MAX_REQ Request maximum reading data...

Страница 33: ...le IN IN IN IN IN IN IN internal circuit internal circuit BCD OUTPUT CONNECTION EXAMPLES MODEL EXTERNAL DIMENSIONS FCN CONNECTOR PIN ASSIGNMENT HDR40 L TO 47Dx TO CONNECTING DEVICE 38 1 50 47 1 85 Con...

Страница 34: ...iring Make sure that the saturation voltage residual voltage of an input device meets the detecting levels of the unit Other wise the unit may not operate correctly I O options code 6 A TIMING 12 11 1...

Страница 35: ...Max 12 VA R 24 V DC 10 approx 3 5 W P 110 V DC 85 to 150 V DC approx 3 5 W IMPORTANT For safety make sure that wiring is performed by qualified personnel only In order to prevent potential electric s...

Страница 36: ...e installing separating the terminal block EVENT TRIGGER INPUT AND ALARM OUTPUT PHOTO MOSFET RELAY The Euro type connector terminal block is separable To install confirm the direction and insert the u...

Страница 37: ...g until it clicks into place Press the unlocking buttons on the right and left sides of the connector to remove IMPORTANT Be sure to turn off the power supply input signal and power supply to the outp...

Страница 38: ...eter in the concave part B of the terminal cover and push the cover until it clicks into place REMOVING TERMINAL COVER a Insert the minus tip of a screwdriver into a hole at the lower left corner of t...

Страница 39: ...and display scaling is as shown in the following figure and chart Input type Type of input signal to 47DAC measuring range Input scaling 0 input value input scaling value Zero and 100 input value inp...

Страница 40: ...TING PROCEDURE The basic setting procedure is as follows 1 Confirm the wiring turn on the power and move on to Scaling Setting Mode measurement stopped Hold down Scale button for 3 seconds or more 2 S...

Страница 41: ...most significant digit starts blinking 2 Press Shift and Up buttons to set a numerical value Press Shift button to go to the next digit Press Up button to change the blinking value 3 Press Alarm or S...

Страница 42: ...setting The next or previous parameter setting is indicated DECIMAL POINT POSITION SELECTION 1 Press Shift button to shift the display into the setting standby mode The current set value starts blink...

Страница 43: ...in Alarm Setting and Advanced Setting Modes Refer to 32 LIMITING BUTTON OPERATION to change the lockout level Configurable with the level LV0 Configurable with the level LV0 or LV1 default INVALID PAR...

Страница 44: ...with parameter display The alarm indication is due to the last status before mode transi tion held but does not show the unit failure ORDER TO DISPLAY PARAMETERS Some parameters may not be displayed d...

Страница 45: ...small input signal can be set within the setting range of an input type however the accuracy will be worse Choose appropriate input type and code The input and display scaling values bargraph lower a...

Страница 46: ...V 2V Measuring range 0 2 V 0 000 2 000 V 0 2 2 V 20V Measuring range 0 20 V 0 000 20 000 V 0 22 V 200V Measuring range 0 200 V 0 00 200 00 V 0 220 V INPUT CODE 2 MODEL 47DAC 2XX XX MAIN DISPLAY FUNCTI...

Страница 47: ...h shows the input out of the meas uring range and does not show the unit failure The SD indicates the bank No with the bank switching set to ena bled 2 Hold down Scale button for 3 seconds or more to...

Страница 48: ...O QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode NOTE INPUT TYPE Input type cannot be changed across different input codes input code 1 to 2 for example IF THE F...

Страница 49: ...input type is not available Input scaling value Zero and input scaling value Span can be adjusted by applying actual input signals Refer to 33 1 TEACH CALIBRATION for details DISPLAY SCALING Display...

Страница 50: ...splay Scaling Zero Span Input Input Scaling Inverted Scaling The display value decreases when the input signal increases Input Span Input Scaling Zero Zero Span Display Scaling Display RELATION BETWEE...

Страница 51: ...scaling value Span 0 0000 0 2000 V 0 2 V 2V Input scaling value Zero Input scaling value Span 0 000 2 000 V 0 20 V 20V Input scaling value Zero Input scaling value Span 0 000 20 000 V 0 200 V 200V In...

Страница 52: ...ates the bank No with the bank switching set to ena bled 2 Hold down Scale button for 3 seconds or more to move on to Scaling Setting Mode The input type is indicated The SD indicates INTYPE NOTE Some...

Страница 53: ...g range NG indicator starts blinking when the set value is within invalid range Return the setting within the valid range 6 Press Alarm or Scale button to apply the new setting And the next parameter...

Страница 54: ...default 15 sec in one of the other modes This time period automatic return time is configurable Refer to 15 GOING BACK AUTOMATICALLY TO MEASUR ING MODE TO ABORT A SETTING Hold down Max Min button for...

Страница 55: ...E 0 0 2 V 0 2V Display scaling value Zero Display scaling value Span to 0 2 V 2V Display scaling value Zero Display scaling value Span 0 20 V 20V Display scaling value Zero Display scaling value Span...

Страница 56: ...ates the bank No with the bank switching set to ena bled 2 Hold down Scale button for 3 seconds or more to move on to Scaling Setting Mode The input type is indicated The SD indicates INTYPE NOTE Some...

Страница 57: ...e decimal point position setting Disregard the decimal point here The negative sign must be set to the 6th digit For example set 004 00 instead of 4 00 6 Press Alarm or Scale button to apply the new s...

Страница 58: ...This time period automatic return time is configurable Refer to 15 GOING BACK AUTOMATICALLY TO MEASUR ING MODE TO ABORT A SETTING Hold down Max Min button for 1 second or more in the setting standby m...

Страница 59: ...NOTE Indication S ERR may blink which shows the input out of the meas uring range and does not show the unit failure The SD indicates the bank No with the bank switching set to ena bled 2 Hold down Sc...

Страница 60: ...Up button to change the blinking value NOTE 020 000 is a display example Set any value within the setting range NG indicator starts blinking when the set value is within invalid range Return the sett...

Страница 61: ...default 15 sec in one of the other modes This time period automatic return time is configurable Refer to 15 GOING BACK AUTOMATICALLY TO MEASUR ING MODE TO ABORT A SETTING Hold down Max Min button for...

Страница 62: ...e NOTE Indication S ERR may blink which shows the input out of the meas uring range and does not show the unit failure The SD indicates the bank No with the bank switching set to ena bled 2 Hold down...

Страница 63: ...00 is a display example Set any value within the range of 20000 to 100000 The decimal point position depends on the decimal point position setting Disregard the decimal point here The negative sign mu...

Страница 64: ...This time period automatic return time is configurable Refer to 15 GOING BACK AUTOMATICALLY TO MEASUR ING MODE TO ABORT A SETTING Hold down Max Min button for 1 second or more in the setting standby m...

Страница 65: ...position per input type when the input type has been changed INPUT CODE 1 MODEL 47DAC 1XX XX INPUT TYPE MAIN DISPLAY DEFAULT VALUE 0 0 2 V 0 2V 4 decimal places 10 4 0 2 V 2V 3 decimal places 10 3 0 2...

Страница 66: ...E Indication S ERR may blink which shows the input out of the meas uring range and does not show the unit failure The SD indicates the bank No with the bank switching set to ena bled 2 Hold down Scale...

Страница 67: ...s 5 Press Up button to select the decimal point position Select 2 decimal places 10 2 Press Up button to move the decimal point NOTE The right figure shows a display example Select one among no decima...

Страница 68: ...wn Max Min button for 1 second or more in the setting standby mode indication blinking in Step 4 and 5 to return to Measuring Mode without applying the last changes If you get lost in a setting mode y...

Страница 69: ...specification voltage current When the indication is shifted with FZ and or TZ indicators on the Forced Zero or Tare Adjustment is being executed Cancel the Forced Zero and Tare Adjust ment Refer to...

Страница 70: ...Setting Basic settings such like input type input scaling and display scaling and also Teach Calibration bargraph settings analog output settings and analog output adjust ments can be performed Measu...

Страница 71: ...E TO MEASURING MODE Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode Measuring Mode Lockout Setting Mode POWER ON Alarm Setting Mode Advanced Setting Mode Hold down Ala...

Страница 72: ...00V Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode from each parameter Measuring Mode Input scaling value Zero Display scaling value Zero Input scaling value Span Dis...

Страница 73: ...alarm setpoint LL trip action 2 LL deadband hysteresis 2 LL ON delay time 2 LL coil at alarm 2 Bank No 1 LL OFF delay time 2 LL one shot output 2 Continued on the following page L alarm setpoint L tr...

Страница 74: ...FF delay time 2 L one shot output 2 L coil at alarm 2 HH alarm setpoint H trip action 2 H deadband hysteresis 2 H ON delay time 2 H coil at alarm 2 H OFF delay time 2 H one shot output 2 H alarm setpo...

Страница 75: ...ale Event trigger mode 1 ON timing delay 1 2 OFF timing delay 1 3 Startup timer 1 Averaging time Low end cutout Low end cutout value 4 Automatic return time to Measuring Mode Transition time to Lockou...

Страница 76: ...to Measuring Mode from each parameter Manual sub display reset 5 P output 5 Continued from the previous page Continued from the previous page Latching alarm 5 Alarm power ON delay 5 Standby sequence...

Страница 77: ...plays show default values Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode from each parameter 7 Parameter shifting in Loop Test Output Mode There is no parameter shift...

Страница 78: ...reverse LCD Bidirectional bar Bidirectional bar reverse LCD No bargraph BARGRAPH IMAGE UNIDIRECTIONAL UNIDIRECTIONAL REVERSE LCD BIDIRECTIONAL BIDIRECTIONAL REVERSE LCD Upper limit 100 Present value...

Страница 79: ...upper limit 0 2 mA 2MA Bargraph lower limit Bargraph upper limit 0 20 mA 20MA Bargraph lower limit Bargraph upper limit 0 200 mA 200MA Bargraph lower limit Bargraph upper limit IMPORTANT The bargraph...

Страница 80: ...The bargraph type is indicated The SD indicates BAR GRH 3 Press Shift and Up buttons to select the bargraph type Select one among INC INCR DEV DEVR and OFF 4 Press Alarm or Scale button to apply the n...

Страница 81: ...ANUAL EM 9518 B Rev 4 5 TO GO ON TO SET THE BARGRAPH LOWER LIMIT UPPER LIMIT Skip to Step 2 in 7 2 BARGRAPH LOWER LIMIT UPPER LIMIT TO QUIT Hold down Alarm or Scale button for 1 second or more to retu...

Страница 82: ...he SD indicates BAR L Zro indicator turns on 3 Press Shift button to shift the display into the setting standby mode Then press Shift and Up buttons to set the bargraph lower limit The sixth digit sta...

Страница 83: ...the decimal point position set in the decimal point position setting 6 Press Alarm or Scale button to apply the new value The bargraph upper limit is registered and the next parameter setting is indic...

Страница 84: ...alue DC output proportional to the display value affected by event trigger mode averaging time forced zero tare adjustment low end cutout display refreshing rate round off low digit reading and high p...

Страница 85: ...T TYPE MAIN DISPLAY DEFAULT VALUE 0 0 2 mA 0 2MA Analog output 0 Analog output 100 0 2 mA 2MA Analog output 0 Analog output 100 0 20 mA 20MA Analog output 0 Analog output 100 0 200 mA 200MA Analog out...

Страница 86: ...t type setting The analog output type is indicated The SD indicates ANG TYP 3 Press Shift and Up buttons to select the analog output type Select one among 4 20MA 0 5V 5V 10V and 0 20MA 4 Press Alarm o...

Страница 87: ...ING MANUAL EM 9518 B Rev 4 5 TO GO ON TO SET THE ANALOG OUTPUT FUNCTION MODE Skip to Step 2 in 8 2 ANALOG OUTPUT FUNCTION MODE TO QUIT Hold down Alarm or Scale button for 1 second or more to return to...

Страница 88: ...YPE 2 Press Alarm or Scale button to go to the analog output function mode setting The analog output function mode is indicated The SD indicates ANG VAL 3 Press Shift and Up buttons to select the anal...

Страница 89: ...G MANUAL EM 9518 B Rev 4 5 TO GO ON TO SET THE ANALOG OUTPUTS 0 AND 100 Skip to Step 2 in 8 3 ANALOG OUTPUT 0 ANALOG OUTPUT 100 TO QUIT Hold down Alarm or Scale button for 1 second or more to return t...

Страница 90: ...ated The SD indicates ANG L Zro indicator turns on 3 Press Shift button to shift the display into the setting standby mode Then press Shift and Up buttons to set the analog out put 0 The sixth digit s...

Страница 91: ...e analog output 100 with the decimal point position set in the decimal point position setting 6 Press Alarm or Scale button to apply the new value The analog output 100 is registered and the next para...

Страница 92: ...ks in the direction of increasing the display value for low trip and in the direction of decreasing it for high ON delay time Alarm output is provided when the display value exceeds the setpoint and s...

Страница 93: ...after the ON delay time tH has elapsed P indicator turns off 3 OFF delay time is triggered when the display value falls below the H setpoint P indicator turns on 4 H indicator turns off after the OFF...

Страница 94: ...LL alarm output to high trip action for example LL indicator turns on at alarm Figure 6 ON delay time Figure 7 OFF delay time Display value Alarm setpoint hi ON delay time ON delay time 1 2 Alarm out...

Страница 95: ...s I O option code 2 or 8 SPDT relay 2 points Display value Alarm setpoint Alarm output coil energized Alarm output coil de energized Alarm setpoint Display value Alarm output coil energized N O N C Al...

Страница 96: ...nt e g P and L are not provided with L set to invalid HH alarm setpoint H alarm setpoint L alarm setpoint invalid LL alarm setpoint HH alarm output hi H alarm output hi L alarm output invalid LL alarm...

Страница 97: ...setting 2 Press Shift and Up buttons to select the alarm output pattern Select NORMAL or ZONE 3 Press Alarm or Scale button to apply the new setting And the next parameter setting is indicated NOTE Pr...

Страница 98: ...ault values of alarm setpoints are as shown in the following tables INPUT CODE 1 MODEL 47DAC 1XX XX PARAMETER DEFAULT VALUE LL alarm setpoint L alarm setpoint H alarm setpoint HH alarm setpoint INPUT...

Страница 99: ...le button to go to the LL L H or HH alarm setpoint setting The LL L H or HH alarm setpoint is indicated The SD indicates ALARMLL ALARM L ALARM H or ALARM HH LL L H or HH indicator starts blinking 3 Pr...

Страница 100: ...t set to completely unlock Alarm Set ting Mode Press Scale button and the alarm output pattern ALM PTN on the SD or the LL L or H setpoint ALARMLL ALARM L or ALARM H on the SD will be indicated Or the...

Страница 101: ...y examples The displays depend on the settings 1 Hold down Alarm button for 3 seconds or more to move on to Alarm Setting Mode The alarm output pattern is indicated The SD indicates ALM PTN NOTE With...

Страница 102: ...d will be indicated HYST LL HYST L HYST H or HYST HH on the SD Press Scale button and the LL L H or HH alarm setpoint will be indicated ALARMLL ALARM L ALARM H or ALARMHH on the SD 5 TO GO ON TO SET A...

Страница 103: ...to move on to Alarm Setting Mode The alarm output pattern is indicated The SD indicates ALM PTN NOTE With the bank switching set to enabled via the front button control the bank No is indicated ALM BN...

Страница 104: ...time will be indicated ONDLYLL ONDLY L ONDLY H or ONDLYHH on the SD Press Scale button and the LL L H or HH trip action will be indicated LIMT LL LIMT L LIMT H or LIMT HH on the SD 5 TO GO ON TO SET A...

Страница 105: ...r 3 seconds or more to move on to Alarm Setting Mode The alarm output pattern is indicated The SD indicates ALM PTN NOTE With the bank switching set to enabled via the front button control the bank No...

Страница 106: ...DLYLL OFDLY L OFDLY H OFDLYHH or OFDLY P on the SD Press Scale button and the LL L H or HH deadband HYST LL HYST L HYST H or HYST HH on the SD or the HH coil at alarm RELAYHH on the SD will be indicat...

Страница 107: ...NOTE The one shot output setting prevails the OFF delay time 9 6 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the settings 1 Hold down Alarm button for...

Страница 108: ...or Scale button to apply the new setting And the next parameter setting is indicated NOTE Press Alarm button and the LL L H HH or P one shot output will be indicated SHOT LL SHOT L SHOT H SHOT HH or...

Страница 109: ...n the alarm output turns ON and stops blinking on when it is OFF which enables the one shot output status to be easily recognized 9 7 1 OPERATING PROCEDURE NOTE The following figures are display examp...

Страница 110: ...pply the new setting And the next parameter setting is indicated NOTE Press Alarm button and the LL L H HH or P coil at alarm will be indicated RELAYLL RELAY L RELAY H RE LAYHH or RELAY P on the SD Pr...

Страница 111: ...OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the settings 1 Hold down Alarm button for 3 seconds or more to move on to Alarm Setting Mode The alarm output...

Страница 112: ...P on the SD or the main display blinking at alarm ALMBLNK on the SD will be indicated Press Scale button and the LL L H HH or P one shot output will be indicated SHOT LL SHOT L SHOT H SHOT HH or SHOT...

Страница 113: ...3 second intervals 9 9 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the settings 1 Hold down Alarm button for 3 seconds or more to move on to Alarm Sett...

Страница 114: ...arm output pattern will be indicated ALM PTN on the SD or the bank copy will be indicated BNK CPY on the SD with the bank switching set to enabled via the front button control Press Scale button and t...

Страница 115: ...on control or enabled via Modbus communication the SD indicates the current bank No BANK1 through BANK8 in Measuring Mode When the setting is changed from enabled via the front button control or enabl...

Страница 116: ...3 seconds or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD...

Страница 117: ...E Press Alarm button and the firmware version indication will be indicated FRM VER on the SD or the REQ input logic will be indicated BCD REQ on the SD with the I O option code 5 9 or A Press Scale bu...

Страница 118: ...s Alarm or Scale button to go to the bank copy setting The bank copy is indicated The SD indicates BNK CPY 3 Press Shift and Up buttons to select ON 4 Press Alarm or Scale button to execute the bank c...

Страница 119: ...119 47DAC OPERATING MANUAL EM 9518 B Rev 4 5 TO GO ON TO SET THE BANK NO Skip to Step 2 in 10 3 BANK NO TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode...

Страница 120: ...hift and Up buttons select the bank No Select one among 1 through 8 3 Press Alarm or Scale button to apply the bank No And the next parameter setting is indicated NOTE Press Alarm button and the alarm...

Страница 121: ...selected In order to reset the latching set the latching alarm to no latching turn off the power and restart or provide the RESET signal Alarm power ON delay The measuring can begin after waiting for...

Страница 122: ...he L setpoint The output is held even when it exceeds the L setpoint The display value corresponds to the measured value 2 When the power is turned off and restarted the alarm output is reset 3 The H...

Страница 123: ...e alarm power ON delay time period from power on the alarm output is not provided even when the display value becomes below the L set point 2 After the alarm power ON delay time is elapsed the alarm o...

Страница 124: ...to each setting of the P status The operation of the alarm indicators are not changed even when the P output is set 11 1 1 OPERATING PROCEDURE NOTE The following figures are display examples The displ...

Страница 125: ...e setting 4 Press Alarm or Scale button to apply the new setting And the next parameter setting is indicated NOTE Press Alarm button and the latching alarm will be indicated OUT STP on the SD Press Sc...

Страница 126: ...th the measurement stopped When the input changes significantly and rapidly the held display value may not conform to the last measured value or setpoint 11 2 1 OPERATING PROCEDURE NOTE The following...

Страница 127: ...etting And the next parameter setting is indicated NOTE Press Alarm button and the alarm power ON delay will be indicated PWR DLY on the SD Press Scale button and the P output will be indicated PASS o...

Страница 128: ...ations and settings 1 Hold down Alarm and Scale buttons at once for 3 seconds or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O opti...

Страница 129: ...ting And the next parameter setting is indicated NOTE Press Alarm button and the standby sequence will be indicated STDBY on the SD Press Scale button and the latching alarm will be indicated OUT STP...

Страница 130: ...are effective after power off and restart 11 4 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the specifications and settings 1 Hold down Alarm and Scale...

Страница 131: ...ng And the next parameter setting is indicated NOTE Press Alarm button and the scaling error will be indicated SE ALM on the SD Press Scale button and the alarm power ON delay will be indicated PWR DL...

Страница 132: ...ERR direction The default setting is alarm trip action valid at over range 11 5 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the specifications and set...

Страница 133: ...And the next parameter setting is indicated NOTE Press Alarm button and the round off low digit reading will be indicated STEP on the SD Press Scale button and the standby sequence will be indicated S...

Страница 134: ...ing 50 milliseconds Average Average 1 2 Display value Refreshing display 50 milliseconds averaging time 4 1 The moving average operation starts immediately after the power is on or the averaging type...

Страница 135: ...00 millisecond intervals 8 samples 400 millisecond intervals 16 samples 800 millisecond intervals 32 samples 1 6 second intervals 64 samples 3 2 second intervals 128 samples 6 4 second intervals 256 s...

Страница 136: ...e 6 or A the event trigger mode is indicated EVENT on the SD Press Alarm button to go to the averaging type setting 2 Press Shift and Up buttons to select the averaging type Select MOVING or SIMPLE 3...

Страница 137: ...47DAC OPERATING MANUAL EM 9518 B Rev 4 4 TO GO ON TO SET THE AVERAGING TIME Skip to Step 2 in 12 2 AVERAGING TIME TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring M...

Страница 138: ...or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Al...

Страница 139: ...tting And the next parameter setting is indicated NOTE Press Alarm button and the low end cutout will be indicated ZEROLMT on the SD Press Scale button and the averaging type will be indicated AVE TP...

Страница 140: ...E BETWEEN LOW END CUTOUT AND ABSOLUTE VALUE LOW END CUTOUT Figure 1 Low end cutout ON Figure 2 Absolute value low end cutout ON Low end cutout value Display value 0 Low end cutout value Display value...

Страница 141: ...r 3 seconds or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD...

Страница 142: ...e will be indicated ZLMTN on the SD or the display color will be indicated COLOR on the SD with the low end cutout set to low end cutout OFF Press Scale button and the averaging time will be indicated...

Страница 143: ...E With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button to go to the low end cutout value setting The low end cutout value is indicated The...

Страница 144: ...etting And the next parameter setting is indicated NOTE Press Alarm button and the display color will be indicated COLOR on the SD Press Scale button and the low end cutout will be indicated ZEROLMT o...

Страница 145: ...l to green alarm Red 14 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the specifications and settings 1 Hold down Alarm and Scale buttons at once for 3 s...

Страница 146: ...eter setting is indicated NOTE Press Alarm button and the automatic return time to Measuring Mode will be indicated RETURN on the SD Press Scale button and the low end cutout value will be indicated Z...

Страница 147: ...not go back automatically to Measuring Mode depending on the modes Table 2 TABLE 1 AUTOMATIC RETURN TIME MAIN DISPLAY FUNCTION DEFAULT VALUE Automatic return disabled to 1 to 99 seconds TABLE 2 AUTOMA...

Страница 148: ...ith the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button to go to the automatic return time to Measuring Mode setting The automatic return time...

Страница 149: ...e next parameter setting is indicated NOTE Press Alarm button and the transition time to Lockout Setting Mode will be indicated PROTECT on the SD Press Scale button and the display color will be indic...

Страница 150: ...e below When the input signal changes rapidly the display refreshing rate can be slowed to suppress the display flickering DISPLAY REFRESHING RATE MAIN DISPLAY FUNCTION DEFAULT VALUE 50 milliseconds t...

Страница 151: ...ndicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button to go to the display refreshing rate setting The display refreshi...

Страница 152: ...version indication will be indicated FRM VER on the SD or the manual sub display reset will be indicated S DISP on the SD with the alarm setting lockout set to completely unlock Alarm Set ting Mode Pr...

Страница 153: ...ng can be selected among OFF 1 2 5 and 10 ROUND OFF LOW DIGIT READING MAIN DISPLAY FUNCTION DEFAULT VALUE No round off 1 2 5 10 INDICATION IN ROUNDING OFF LOW DIGIT READING MAIN DISPLAY LOW DIGIT INDI...

Страница 154: ...to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button...

Страница 155: ...ing And the next parameter setting is indicated NOTE Press Alarm button and the display reading type will be indicated M DISP on the SD Press Scale button and the scaling error will be indicated SE AL...

Страница 156: ...ADING REFERENCE USED IN NEXT CALCULATION 1 I1 I1 I1 0 C1 I1 2 I2 I2 C1 C2 1 C1 I2 1 I1 I2 2 2 3 I3 I3 C2 C3 1 C2 I3 1 I1 I2 1 I3 2 4 2 4 I4 I4 C3 C4 1 C3 I4 1 I1 I2 1 I3 1 I4 2 8 4 2 n In In Cn 1 Cn 1...

Страница 157: ...splay scaling settings It is recommended to set the display scaling values setpoints and bargraph lower and upper limits analog outputs 0 and 100 as necessary taking account of this The high pass filt...

Страница 158: ...onds or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Pres...

Страница 159: ...And the next parameter setting is indicated NOTE Press Alarm button and the backlight brightness will be indicated BRIGHT on the SD Press Scale button and the display reading type will be indicated M...

Страница 160: ...adjusted figures below The brightness can be selected in the following table BACKLIGHT BRIGHTNESS MAIN DISPLAY FUNCTION DEFAULT VALUE Brightness level 1 dark Brightness level 2 Brightness level 3 bri...

Страница 161: ...to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or S...

Страница 162: ...etting And the next parameter setting is indicated NOTE Press Alarm button and the LCD contrast will be indicated CNTRAST on the SD Press Scale button and the high pass filter will be indicated HP F o...

Страница 163: ...ed in the following table LCD CONTRAST MAIN DISPLAY FUNCTION DEFAULT VALUE Contrast level 1 low Contrast level 2 Contrast level 3 Contrast level 4 Contrast level 5 middle Contrast level 6 Contrast lev...

Страница 164: ...more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm...

Страница 165: ...ng And the next parameter setting is indicated NOTE Press Alarm button and the bank switching will be indicated BNK CHG on the SD Press Scale button and the backlight brightness will be indicated BRIG...

Страница 166: ...N No measuring for the preset startup timer period from the falling edge in all modes Table 2 HOLD Reading measured signal stops and the last measured value MAX and MIN values and output status are he...

Страница 167: ...Measuring disabled Measuring disabled TIMING RESET OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON Other Measuring disabled Measuring disabled Measuring disabled Measuring disabled TIMING RESE...

Страница 168: ...ement The TIMING signal is invalid DC output Proportional to the display reading For no measured data the value is 0 TABLE 8 PEAK HOLD MODE TIMING signal While the TIMING signal is ON the MAX value wi...

Страница 169: ...f the display refreshing rate When the ZERO signal is ON the Forced Zero and Tare Adjustment can be executed or canceled regardless of the Forced Zero control lockout setting The RESET signal does not...

Страница 170: ...timing delay time shorter than the period when the TIMING signal is ON The ON timing delay and OFF timing delay are disabled with normal selected for the event trigger mode parameter The OFF timing de...

Страница 171: ...ndicates EVENT 2 Press Shift and Up buttons to select the event trigger mode Select one among NORMAL S HLD P HLD B HLD and PP HLD 3 Press Alarm or Scale button to apply the new setting And the next pa...

Страница 172: ...47DAC OPERATING MANUAL EM 9518 B Rev 4 4 TO GO ON TO SET THE ON TIMING DELAY Skip to Step 2 in 21 2 ON TIMING DELAY TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring...

Страница 173: ...cated The SD indicates EVENT 2 Press Alarm or Scale button to go to the ON timing delay setting The ON timing delay is indicated The SD indicates ON TDLY NOTE The ON timing delay is disabled with norm...

Страница 174: ...will be indicated OF TDLY on the SD or the startup timer will be indicated STR TMR on the SD with the event trigger mode set to sampling hold Press Scale button and the event trigger mode will be ind...

Страница 175: ...SD indicates EVENT 2 Press Alarm or Scale button to go to the OFF timing delay setting The OFF timing delay is indicated The SD indicates OF TDLY NOTE The OFF timing delay is disabled with normal or s...

Страница 176: ...indicated NOTE Press Alarm button and the startup timer will be indicated STR TMR on the SD Press Scale button and the ON timing delay will be indicated ON TDLY on the SD 5 TO GO ON TO SET THE STARTUP...

Страница 177: ...nced Setting Mode The event trigger mode is indicated The SD indicates EVENT 2 Press Alarm or Scale button to go to the startup timer set ting The startup timer is indicated The SD indicates STR TMR 3...

Страница 178: ...indicated AVE TP on the SD Press Scale button and the OFF timing delay will be indicated OF TDLY on the SD the event trigger mode will be indicated EVENT on the SD with the event trigger mode set to n...

Страница 179: ...ot be executed or canceled for no measured data RESET signal ON The MAX and MIN values can be reset with the RESET signal ON regardless of the MAX MIN display control lockout setting The front button...

Страница 180: ...ds after that Output is provided via open collector enabling wired OR gate configuration 2 2 2 3 REQ 1 REQ 2 REQ 3 2 1 OFF ON OFF ON DAV DATA 1 OFF ON OFF ON OFF ON PLC REQ 1 REQ 2 REQ 3 47Dx 1 47Dx 2...

Страница 181: ...nce for 3 seconds or more to move on to Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE The event trigger mode is indicated EVENT on the SD with the I O option code...

Страница 182: ...g And the next parameter setting is indicated NOTE Press Alarm button and the status output logic will be indicated BCD STA on the SD Press Scale button and the DAV output logic will be indicated BCD...

Страница 183: ...bled only after the power supply has been turned off and on The T1 5 and T3 5 timers are specified as 1 5 and 3 5 characters times in Modbus standard specifications These pa rameters are not necessary...

Страница 184: ...icates EQP NO 2 Press Shift button to shift the display into the setting standby mode Then press Shift and Up buttons to set the device ad dress The third digit starts blinking to which you can apply...

Страница 185: ...GO ON TO SET THE BAUD RATE Skip to Step 2 in 23 2 BAUD RATE TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled only a...

Страница 186: ...icates EQP NO 2 Press Alarm or Scale button to go to the baud rate setting The baud rate is indicated The SD indicates B RATE 3 Press Shift and Up buttons to select the baud rate Select one among 1200...

Страница 187: ...O ON TO SET THE PARITY BIT Skip to Step 2 in 23 3 PARITY BIT TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled only...

Страница 188: ...The SD indicates EQP NO 2 Press Alarm or Scale button to go to the parity bit setting The parity bit is indicated The SD indicates PARITY 3 Press Shift and Up buttons to select the parity bit Select...

Страница 189: ...GO ON TO SET THE STOP BIT Skip to Step 2 in 23 4 STOP BIT TO QUIT Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled only af...

Страница 190: ...s indicated The SD indicates EQP NO 2 Press Alarm or Scale button to go to the stop bit setting The stop bit is indicated The SD indicates STOPBIT 3 Press Shift and Up buttons to select the stop bit S...

Страница 191: ...RATING MANUAL EM 9518 B Rev 4 5 Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled only after the power supply has been turne...

Страница 192: ...ndicated The SD indicates EQP NO 2 Press Alarm or Scale button to go to the T1 5 timer setting The T1 5 timer is indicated The SD indicates T15 NOTE The SD indicates T35 with the T3 5 timer 3 Press Sh...

Страница 193: ...ress Scale button and the stop bit will be indicated STOPBIT on the SD 5 Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled o...

Страница 194: ...The SD indicates EQP NO 2 Press Alarm or Scale button to go to the long register set ting The long register is indicated The SD indicates L WORD 3 Press Shift and Up buttons to select the long regist...

Страница 195: ...RATING MANUAL EM 9518 B Rev 4 5 Hold down Alarm or Scale button for 1 second or more to return to Measuring Mode IMPORTANT Modbus setting changes are enabled only after the power supply has been turne...

Страница 196: ...put is saturated at approximately 10 or 110 e g With the DC output 4 20 mA DC the output can be provided within the range of 2 4 to 21 6 mA DC NOTE Loop Test Output Mode can be used only with the DC o...

Страница 197: ...he DC alarm and BCD outputs The current indication starts blinking to which you can apply changes The SD indicates TEST UP NOTE In moving on to Loop Test Output Mode while S ERR is indicated 110 of th...

Страница 198: ...utton to control it toward the desired output value Hold down Up button to control at high speed The DC and BCD outputs change according to the display value When the display value reaches the desired...

Страница 199: ...e bank switching is set to disabled the bank No is not indicated The alarm setpoints cannot be confirmed when the alarm setting lockout is set to lock Alarm Setting Mode Switching the banks is not ava...

Страница 200: ...gs 1 Press Alarm button to indicate the LL alarm setpoint on the SD The SD indicates the LL alarm setpoint LL indicator starts blinking 2 Press Shift button to shift the SD into the setting standby mo...

Страница 201: ...ted LL indicator turns off and L indicator starts blinking 5 TO GO ON TO SET OTHER ALARM SETPOINTS Repeat operation from Step 2 TO RETURN TO THE BANK NO INDICATION Press Alarm button several times NOT...

Страница 202: ...e 25 2 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the specifications and settings 1 Hold down Alarm and Scale buttons at once for 3 seconds or more to...

Страница 203: ...ting And the next parameter setting is indicated NOTE Press Alarm button and the P output will be indicated PASS on the SD Press Scale button and the display refreshing rate will be indicated D REFSH...

Страница 204: ...s not limit the control with the ZERO signal DISPLAY VALUE IN EXECUTING AND CANCELING FORCED ZERO AND TARE ADJUSTMENT The display value changes as shown in the following figures when Forced Zero and T...

Страница 205: ...ess Up button in Measuring Mode to execute the Forced Zero 2 Press Up button in Forced Zero mode to execute the Tare Adjustment 3 Hold down UP button for 1 second or more to cancel the Tare Adjustment...

Страница 206: ...or canceled while S ERR is indicated though the values are not warranted The Forced Zero and Tare Adjustment cannot be executed or canceled for no measured data RESET signal ON The reference values i...

Страница 207: ...a the front button control but does not limit indication with the BCD output or via Modbus communication and reset with the RESET signal or via Modbus communi cation MAX AND MIN VALUES MAX and MIN val...

Страница 208: ...IN values are reset when the power is turned off NOTE The MAX and MIN values are not reset even when the Forced Zero or Tare Adjustment is executed or canceled The MAX and MIN values are not indicated...

Страница 209: ...G PROCEDURE NOTE The following figures are display examples The displays depend on the specifications and settings 1 Hold down Alarm and Scale buttons at once for 3 seconds or more to move on to Advan...

Страница 210: ...And the next parameter setting is indicated NOTE Press Alarm button and the high pass filter will be indicated HP F on the SD Press Scale button and the round off low digit reading will be indicated...

Страница 211: ...AINING MEASUREMENT STATUS NOTE While the HOLD signal is ON other signals except the RESET signal are invalid The S ERR indication or no measured data is held with the HOLD signal ON The Forced Zero an...

Страница 212: ...D outputs including the status and DAV signals turn OFF However some BCD outputs may be ON depending on the output logic settings The Forced Zero or Tare Adjustment cannot be executed or canceled whil...

Страница 213: ...in the following cases To configure the same settings to several units To confirm the current settings with a PC To make a backup file for failure PROCEDURE TO MOVE ON TO INFRARED COMMUNICATION MODE 1...

Страница 214: ...be affected by sunlight fluorescent lightings employing inverter technology and so forth Try at a shorter distance if communication is not established The COP IRU can communicate with single panel me...

Страница 215: ...Scaling Setting Mode Lock Scaling Setting Mode Advanced setting lockout Completely unlock Advanced Setting Mode Partially unlock Advanced Setting Mode Lock Advanced Setting Mode Modbus setting lockou...

Страница 216: ...cated The SD indicates AL PRT 2 Press Shift and Up buttons to select the alarm setting lockout Select one among LV1 LV2 and LV0 NOTE Select OFF or ON depending on the parameters 3 Press Alarm or Scale...

Страница 217: ...indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button to go to the transition time to Lockout Setting Mode setting The...

Страница 218: ...t parameter setting is indicated NOTE Press Alarm button and the display refreshing rate will be indicated D REFSH on the SD Press Scale button and the automatic return time to Measuring Mode will be...

Страница 219: ...ion on handling them 33 1 1 TEACH CALIBRATION FLOW The Teach Calibration is carried out as shown in the following flowchart IMPORTANT The calibration adjustment in the flow above is applicable to the...

Страница 220: ...efore carrying out the Teach Calibration 2 Press Alarm or Scale button to go to the input scaling value Zero setting The input scaling value Zero is indicated The SD indicates IN A Zro and Tch indicat...

Страница 221: ...ors turn on NOTE Skip to Step 8 when the teach calibration Span is not necessary 6 Press Up button to go to the teach calibration Span setting The present input is indicated Tch indicator starts blink...

Страница 222: ...own in the following flowchart IMPORTANT Warm up measuring instruments equipment and other devices on site for the time specified in each manual and oper ate the unit in a stable condition Adjustable...

Страница 223: ...NTYPE IMPORTANT Warm up the unit for 10 minutes or more before carrying out the Analog Output Adjustment 2 Press Alarm or Scale button to go to the analog output 0 adjustment The analog output 0 adjus...

Страница 224: ...put 0 adjustment is registered The analog output 100 adjustment is indicated The SD indicates AADJ H Zro indicator turns off and Spn indicator turns on NOTE Skip to Step 9 when the analog output 100 a...

Страница 225: ...nalog output 100 adjustment is registered The next parameter is indicated NOTE Press Alarm button and the input type will be indicated INTYPE on the SD Press Scale button and the analog output 0 adjus...

Страница 226: ...unit Make sure that abnormality such like smokes unusual smell or abnormal noises is not found Using the unit continu ously with such abnormality may result in a fire or electric shock Check the termi...

Страница 227: ...Internal data error Repair is needed if the display does not recover after the power is reset A D converter error Repair is needed if the display does not recover after the power is reset Note The me...

Страница 228: ...ion Be careful that the initialization does not recover the ex factory settings 35 2 1 OPERATING PROCEDURE NOTE The following figures are display examples The displays depend on the settings 1 Hold do...

Страница 229: ...Advanced Setting Mode The averaging type is indicated The SD indicates AVE TP NOTE With the I O option code 6 or A the event trigger mode is indicated EVENT on the SD 2 Press Alarm or Scale button to...

Страница 230: ...setting mode Bank No alarm output pattern HH H L and LL alarm setpoint HH H L and LL trip action HH H L and LL deadband hysteresis HH H L LL and P ON delay time HH H L LL and P OFF delay time HH H L...

Страница 231: ...setpoints can be set and indicated regardless of alarm output options Each is independently set either for Hi or Lo alarm trip LL indicator Turns on in red when the LL alarm is tripped L indicator Tur...

Страница 232: ...prox 100 Input type 2MA Measuring range 0 2 mA Operational range 0 2 2 mA Input impedance Approx 100 Input type 20MA Measuring range 0 20 mA Operational range 0 22 mA Input impedance Approx 1 Input ty...

Страница 233: ...bps Max number of nodes 31 except the master Protocol Modbus RTU Parity None odd or even Stop bit 1 bit 2 bits Node address 1 to 247 Media Shielded twisted pair cable CPEV S 0 9 dia Terminating resis...

Страница 234: ...ing humidity 30 to 90 RH non condensing Mounting Panel flush mounting Weight 300 g 0 66 lb PERFORMANCE Accuracy Display 0 5 10 digits with input 5 100 Output 0 1 DC output display output Temp coeffici...

Страница 235: ...odbus RTU 9 Alarm output N O photo MOSFET relay 4 points BCD output A Event trigger input BCD output 4 POWER INPUT AC Power M2 100 240 V AC operational voltage range 85 264 V 50 60 Hz DC Power R 24 V...

Страница 236: ...0 200 mA Input scaling value Zero 1 0 0000 0 2000 to V AC 0 000 2 000 to 0 000 20 000 to 0 00 200 00 to 2 0 0000 0 2000 to mA AC 0 000 2 000 to 0 000 20 000 to 0 00 200 00 to Display scaling value Zer...

Страница 237: ...output Analog output 100 adjustment Adjustable range 0 to 105 increasing decreasing 100 output Teach calibration Zero Teach calibration Span Alarm setting Bank No 1 to 8 to Alarm output pattern Normal...

Страница 238: ...9999 to 100 ms H coil at alarm Coil energized at alarm de energized at alarm HH alarm setpoint 20000 100000 to 1 1 User defined 2 HH trip action High trip low trip HH deadband hysteresis 0000 9999 to...

Страница 239: ...ed 01 99 to Second Transition time to Lockout Setting Mode 00 99 to Second Display refreshing rate 00 0 99 9 to Second Manual sub display reset Alarm setpoint display automatically reset alarm setpoin...

Страница 240: ...s Parity bit None odd even Stop bit 1 or 2 bit s T1 5 timer 01 to 60 to 0 1 T3 5 timer 01 to 60 to 0 1 Long register Low digit word at lower address high digit word at lower address Lockout setting Al...

Страница 241: ...ANGE SUB DISPLAY INDICATOR MAIN DISPLAY DEFAULT VALUE DECIMAL POINT POSITION UNIT Infrared communi cation IR communication display blinking Loop test output Loop test output 20000 100000 to display bl...

Страница 242: ...E The display reading type after power on can be changed to MAX value or MIN value with the display reading type set ting POWER ON Present value Measurement stopped To each mode Executing canceling Fo...

Страница 243: ...alarm setting lockout set to LV2 Alarm setpoints can be confirmed whenever in Measuring Mode except in error indication excluding S ERR POWER ON To each mode L alarm setpoint LL alarm setpoint Confirm...

Страница 244: ...to 100000 Input scaling value Span 0 00 200 00 depending on input types Display scaling value Span 20000 to 100000 No decimal point 10 1 to 10 4 Decimal point position Bargraph type INC unidirectional...

Страница 245: ...L ON delay time 0 0 99 9 sec L coil at alarm EN coil energized DN coil de energized L OFF delay time 0 0 99 9 sec L one shot output 0 0 999 9 sec H alarm setpoint 20000 to 100000 H trip action HIGHI h...

Страница 246: ...3 sec for 1 sec Measurement started Measurement stopped Measuring Mode or Bank No 1 8 Alarm output pattern Normal Zone LL alarm setpoint 20000 to 100000 L alarm setpoint 20000 to 100000 H alarm setpo...

Страница 247: ...ckout Setting Mode 0 0 99 9 sec Display refreshing rate OFF automatically reset ON manually reset Manual sub display reset P output OFF no P output LL alarm setpoint LL L alarm setpoint L H alarm setp...

Страница 248: ...peak to peak hold ON timing delay 0 0 999 9 sec Startup timer 0 0 99 9 sec OFF timing delay 0 0 999 9 sec Averaging type MOVING moving average SIMPLE simple average OFF 2 4 8 16 32 64 128 256 512 Ave...

Страница 249: ...surement started Measurement stopped Measuring Mode or Modbus Setting Mode Device address 1 247 1200 2400 4800 9600 19200 38400 bps Baud rate Non odd even Parity bit 1 2 bit s Stop bit T1 5 timer 0 1...

Страница 250: ...k ON lock MAX MIN display control lockout LV0 unlock MAX MIN display control LV1 lock MAX MIN display reset LV2 lock MAX MIN display control Forced zero control Up button lockout LV0 unlock Forced Zer...

Страница 251: ...251 47DAC OPERATING MANUAL EM 9518 B Rev 4 36 5 CHARACTER SET NUMERALS AND NEGATIVE SIGN 0 1 2 3 4 5 6 7 8 9 ALPHABET A B C D E F G H I J K L M N O P Q R S T U V W X Y Z...

Отзывы: