47DAC OPERATING MANUAL EM-9518-B Rev.4
33.2 ANALOG OUTPUT ADJUSTMENT
You can compensate deviation between the DC output and a device on site by the Analog Output Adjustment function.
Please note that M-System does not warrant the result of your own adjustment.
The internal adjustment data is overwritten every time the unit is adjusted and it is stored even if the power is turned off.
However the data will be lost after an initialization.
33.2.1 ANALOG OUTPUT ADJUSTMENT FLOW
The Analog Output Adjustment is carried out as shown in the following flowchart.
IMPORTANT
• Warm up measuring instruments, equipment and other devices on site for the time specified in each manual, and oper-
ate the unit in a stable condition.
• Adjustable ranges:
Analog output 0% adjustment -5 to +100%
Analog output 100% adjustment 0 to 105%
• Adjust analog output 100% in the following condition:
Analog output 0% + 5% of output span ≤ Analog output 100%
• The analog output is adjustable beyond the above ranges and condition. However the accuracy is not warranted.
Analog output 0% adjustment
POWER ON
Warming up (10 min. or more)
Analog output 100% adjustment
Moving on to Scaling Setting Mode
Back to Measuring Mode
Measurement started
Readjustment
Adjustment completed
Confirming output
(operation check)