224
47DAC OPERATING MANUAL EM-9518-B Rev.4
4
Press Up button until the desired output value.
IMPORTANT
• Confirm that the output signal is stable before pressing Up button while in checking it with a receiving instrument or a
tester.
• Adjustable range is -5 to +100%.
5
Press Alarm/
↓
button to register the analog output 0% adjust-
ment and go to the analog output 100% adjustment.
• The analog output 0% adjustment is registered.
• The analog output 100% adjustment is indicated.
• The SD indicates ‘AADJ H’.
• ‘Zro’ indicator turns off and ‘Spn’ indicator turns on.
NOTE
Skip to Step 9 when the analog output 100% adjustment is not necessary.
6
Press Shift button to switch the signal to increase (indication
‘UP’) or decrease (‘DOWN’).
7
Press Up button until the desired output value.
IMPORTANT
• Confirm that the output signal is stable before pressing Up button while in checking it with a receiving instrument or a
tester.
• Adjustable range is 0 to 105%.
Blinking
Blinking
■
Increasing output
■
Decreasing output