47DAC OPERATING MANUAL EM-9518-B Rev.4
33.2.2 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Scale/
↑
button for 3 seconds or more to move on to
Scaling Setting Mode.
• The input type is indicated.
• The SD indicates ‘INTYPE’.
IMPORTANT
Warm up the unit for 10 minutes or more before carrying out the Analog Output Adjustment.
2
Press Alarm/
↓
or Scale/
↑
button to go to the analog output 0%
adjustment.
• The analog output 0% adjustment is indicated.
• The SD indicates ‘AADJ L’.
• ‘Zro’ indicator turns on.
NOTE
Skip to Step 5 when the analog output 0% adjustment is not necessary.
3
Press Shift button to switch the signal to increase (indication
‘UP’) or decrease (‘DOWN’).
2,5,
8,9
1,2,
8,9
3,6
4,7
Blinking
Blinking
■
Increasing output
■
Decreasing output