9.1.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the settings.
1
Hold down Alarm/
↓
button for 3 seconds or more to move on
to Alarm Setting Mode.
• The alarm output pattern is indicated.
• The SD indicates ‘ALM PTN’.
NOTE
With the bank switching set to “enabled via the front button control”, the bank No. is indicated (‘ALM BNK’ on the SD).
Press Alarm/
↓
button to go to the alarm output pattern setting.
2
Press Shift and Up buttons to select the alarm output pattern.
• Select ‘NORMAL’ or ‘ZONE’.
3
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
• And the next parameter setting is indicated.
NOTE
• Press Alarm/
↓
button, and the LL alarm setpoint will be indicated (‘ALARMLL’ on the SD).
• Press Scale/
↑
button, and the main display blinking at alarm will be indicated (‘ALMBLNK’ on the SD), or the bank No.
will be indicated (‘ALM BNK’ on the SD) with the bank switching set to “enabled via the front button control”.
4
■
TO SET THE NEXT PARAMETER,
Skip to Step 2 in “9.2 ALARM SETPOINT”.
■
TO QUIT,
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
1,3
3
2
2