7.7.3 Save all parameters to FC via ID Switches
All parameters can be saved by the drive itself to the inserted FC.
Preconditions:
A valid FC must be inserted in the socked M1.
The drive must be powered up or rebooted with the inserted M1.
If no FC is inserted, the drive ignores the command and starts up normally.
Steps
Description
1
Set ID switches S1/S2 to FDh.
2
Power cycle the drive.
3
Wait until LEDs L3 and L4 blink together red and green with ca. 4 Hz.
If the drive starts up normally, no flash card is detected.
4
Set ID switches S1/S2 to 11h.
5a
No Error
The blinking stops.
The drive safes the configuration and boots automatically.
Wait until the drive has booted completely.
5b
Error
In case of an error, the L3 and Error LEDs are alternating blinking at ca. 2 Hz.
Possible errors:
The flash card is not compatible (no LinMot-Card, wrong type, …)
The flash card is not writable.
The flash Card is removed during operation.
Required actions:
Check the error cause.
Reboot the drive.
Table 34: Safe all parameters to FC