6.1.2.3.8 X50 Safe Brake
X50
Safe Brake
5
4
3
2
1
Do not connect
Do not connect
PE
Safe Brake-
Safe Brake+
Spring cage connectors
(have to be ordered
separately: see
chapter 6.1.3 )
Use brake, which is engaged when not powered.
Use 24 V brake or valve.
Maximal current: 0.8 A
At 24 V a minimal current of 10 mA must flow
The brake must be active (braking), when the current is equal or below 10mA.
Brake must be tolerant for test pulses in high state of 1ms every 900 ms.
Mating connector (Art. Nr. 0150-4392):
Conductor cross section: 0.2 mm² ... 1.5 mm²
Stripping length 6 mm
Clamping screw: M 2
Screwdriver blade: 0.4 x 2.5 (DIN 5264)
Plugging cycles: 25
Tightening torque (wire connection): 0.2 Nm ... 0.25 Nm
Tightening torque (screw flange): 0.15 Nm ... 0.2 Nm
Use 60/75 °C copper conductors only)
Table 14: X50 Connector. Safe Brake
2S Drive Systems / 0185-1174_E_1V1_SM_C1251-2S / NTI AG
0185-1174_E_1V1_SM_C1251-2S / 2021-11-26 16:43 (Rev. 12500)
Page 42 of 150