9.3.2 Using no Configuration
All parameters and setting on the drives must be done. This can be done with LinMot-Talk, its manual can be found in
[6]. Setup the following parts:
Start the motor wizard, which guides through the configuration of the motor and its application (load, mounting,
cable length, friction, …).
Safety parameters, see chapter 7.5 - Safety Parameters Overview and following.
Setup additional non-safe parameters, those which are not covered by the motor wizard.
Define curves in LinMot-Talk, if necessary.
Define the command table (CT) in LinMot-Talk, if necessary.
Set the correct safe bus address on safe address switches S11/S12
Set correct bus address on the ID switches S1/S2
9.4 Safety Parameter Verification and Validation
Before the safety parameters become active, they have to be verified and validated. (It is not relevant, if the
configuration has imported from or it has created).
Follow the instructions in chapter 7.6.2 - Validate the Safety Parameters.
The LinMot system can now be started and the functional tests can be done. If modifications in the configuration have to
be done, go back to chapter 9.3.2 - Using no Configuration
9.5 Acceptance Tests
Before the machine can be operatively used fulfilling the functional safety requirements, the acceptance tests and the
machine documentation has to be done. This is described in chapter
.