4.6 Diagnostic LEDs
Five LEDs located in the rear side of the connection cap are designed to show
the operating or fault status of the EtherCAT® interface.
The LEDs operation is according to the EtherCAT specifications, see
ETG1300_S_R_V1i1i0_IndicatorLabelingSpecification.pdf.
LED states
Definition
ON
The indicator shall be constantly ON.
OFF
The indicator shall be constantly OFF.
Flickering
The indicator shall turn ON and OFF iso-phase with a frequency
of 10 Hz: ON for 50 ms and OFF for 50 ms.
Blinking
The indicator shall turn ON and OFF iso-phase with a frequency
of 2.5 Hz: ON for 200 ms followed by OFF for 200 ms.
Single flash
The indicator shall show one short flash (200 ms) followed by a
long OFF phase (1000 ms).
Double flash
The indicator shall show a sequence of two short flashes (200
ms), separated by an OFF phase (200 ms), and followed by a
long OFF phase (1000 ms).
L/A Link/ Activity
(
yellow
)
It shows the state of the physical links (IN and OUT)
and the activity in the links
OFF
condition: port closed, link: YES, activity: N.A.
FLICKERING
condition: port open, link: YES, activity: YES
ON
condition: port open, link: YES, activity: NO
RUN
(
green
)
It shows the state of the EtherCAT State Machine
(ESM)
OFF
The encoder is in
INIT
state
BLINKING
The encoder is in
PRE-OPERATIONAL
state
SINGLE FLASH
The encoder is in
SAFE-OPERATIONAL
state
ON
The encoder is in
OPERATIONAL
state
FLICKERING
The encoder is in
BOOT
state
PWR
(
green
)
It shows the power supply state
OFF
The encoder is switched OFF
ON
The encoder is switched ON
ERR
(
red
)
It shows the error state
OFF
No error
FLICKERING
Error while loading parameters from flash memory
at start-up; encoder parameters have not been
saved correctly on flash memory
BLINKING
Invalid configuration
SINGLE FLASH
Local error (see ETG1000.6)
DOUBLE FLASH
Watchdog timeout
ON
Memory error and ESC controller not active
MAN SFA_5000_10000_EC E 1.0.odt